When the interlock is missing or fails in a forward-reverse circuit, both contactors close and bolt two supply phases together through the main contacts, with short-circuit currents of several kiloamperes. This article analyses the physical process, typical scenarios and prevention from design through acceptance.
With KM1 and KM2 closed together, KM1 feeds L1 to U and L3 to W while KM2 feeds L1 to W and L3 to U, so phases L1 and L3 form a metallic loop through the two sets of main contacts. The current is limited only by line impedance and reaches more than ten times rated, which the contacts cannot break; the arc sustains, fuses blow or the breaker trips instantly, and in bad cases contacts weld, busbars burn and the cabinet catches fire.
Typical scenarios: interlock contacts simply omitted in drawing or wiring; NC wired as NO so the logic fails; welded contacts that the electrical interlock cannot open with no mechanical latch as backup; or an interlock wire forgotten after maintenance. Frequent jogging and quick reversal carry the highest risk because operators press both buttons in rapid succession. Prevention needs double protection by design, a no-load press-both-buttons test before energizing, correct instantaneous short-circuit settings, and retesting the interlock after every repair. Never mask frequent tripping by upsizing fuses; that removes the protection.
| Scenario | Risk | Prevention |
|---|---|---|
| Interlock omitted | Both close, short | Check wiring point by point |
| NC wired as NO | Interlock void | Verify contact type before power |
| Welded contacts | Electrical cut fails | Add mechanical latch |
| Not restored after repair | Hidden hazard | Retest before energizing |
| Frequent reversing | High dual-close odds | Double interlock plus delay |
| Upsizing fuses blindly | Protection removed | Find root cause, keep rating |
A missing interlock is the worst fault a reversing circuit can have; one event can burn the whole cabinet. Guard with three gates: double interlock on the drawing, the press-both test before power, and sound protection settings in service.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB 14048.4 for apparatus, GB/T 13539 and GB 14048.2 for short-circuit coordination, GB/T 5226.1 and IEC 60204-1 for machinery safety. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.