A symbol tells you what the part is; a reference designation tells you which one it is. This page covers how to assign device tags, where to place them around symbols, and how to keep drawings, tags and hardware matched through the life of the plant.
Every device carries one unique letter code: KM1 for a contactor, FR1 for a thermal relay, SB1 for a pushbutton, following GB/T 7159 or the company standard. Once assigned, a tag never changes and never gets recycled; retired tags are logged and frozen, so six months later drawings still match nameplates. Identical devices share the letter and differ in the number: KM1 to KM5 for five contactors, numbered without gaps unless expansion positions are reserved.
Placement follows convention: above or left of contacts, right of coils, terminal numbers directly on terminal blocks. For cross-page references add the zone number next to the contact, for example coil in zone 7 and contacts in zone 12; an experienced electrician collects all contacts of one relay in seconds using these zones. Tags on terminal diagrams must match the schematic character by character, including subscript style: KM1 is never written as K1 or km1.
On the floor, follow the chain of drawing, tag, terminal, hardware: find the tag on the schematic, read the terminal diagram for the wiring numbers, then match the nameplate in the cabinet. Fit every device with a tag plate equal to its drawing tag; when maintenance says replace FR2, everyone knows which relay. Tag new machines before wiring, and correct legacy mismatches during scheduled overhauls with a logged change.
| Device | Letter code | Placement | Example |
|---|---|---|---|
| Contactor | KM | Above contacts / right of coil | KM1, KM2 |
| Thermal relay | FR | Beside symbol | FR1 |
| Pushbutton | SB | Beside contact | SB1 start, SB2 stop |
| Circuit breaker | QF | Beside symbol | QF1 |
| Auxiliary relay | KA | Above contacts / right of coil | KA1 to KA6 |
| Pilot lamp | HL | Beside symbol | HL1 run, HL2 fault |
| Control transformer | TC | Beside symbol | TC1 |
Reference designations are the identity system of a drawing set: prefer a longer tag over ambiguity. Publish one plant-wide designation rule covering letter meanings, subscript format and cross-page references, and ship it with every drawing handover.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Designation codes per GB/T 7159; symbols and marking per GB/T 4728. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.