Setting thermal relay currents in two-speed motor control

A two-speed motor draws different rated currents in its two speeds, and one wrong thermal setting defeats the protection. This page covers split thermal protection per branch, how to compute each setting, trip class choice and reset mode selection.

1. How it works

Two-speed machines need one thermal relay per speed branch: FR1 in series with the KM1 low-speed path, FR2 with the KM2 high-speed path, each set to the nameplate current of its own winding, typically 12A and 15A on a constant-power unit. The dial allows fine adjustment within a few percent, so set it on the nameplate value. Using a single relay for both speeds, a widespread design error, matches the heating characteristic of one speed and leaves the other under-protected; it is only acceptable when the two currents are nearly equal, and even then the setting at the larger value reduces sensitivity for the smaller one.

2. Numbers and practice

Setting procedure: take both nameplate currents; confirm whether the plate gives line current, and for delta connections the line current exceeds the winding current by root three, so use the line value; apply ambient correction only above forty degrees in the cabinet unless the relay is compensated; and check the trip class against starting time, fans that take more than five seconds to spin up need class 20 rather than the standard class 10, or the relay trips mid-start. Validate by clamping the running current after an hour: anything persistently above ninety-five percent of the setting means the dial is tight or the load is abnormal.

3. Pitfalls and fixes

Reset mode follows safety grade: auxiliary drives use auto-reset, restoring after about five minutes, so a night trip does not idle the plant unattended; main drives use manual reset to force a human to confirm the overload before re-energizing. Wire each thermal contact into its own branch control circuit, never cross them: a crossed pair lets a low-speed trip lock out high speed too and doubles troubleshooting time. Tight terminals matter, poor joints heat the relay into nuisance trips. Verify the trip characteristic annually and replace beyond ten percent error.

4. Thermal relay settings for two-speed motors

ItemLow-speed FR1High-speed FR2Note
Series positionIn KM1 branchIn KM2 branchEach guards its own speed
Setting currentNameplate low-speed valueNameplate high-speed valueDial on the nameplate figure
Trip classPer starting timeClass 10 or 20Long-start fans take class 20
Reset modeAuto for auxiliariesManual for main drivesBy safety grade
Temperature correctionAbove 40C in cabinetSameCompensated types skip it
Annual checkTrip characteristic testSameReplace beyond 10% error

5. Notes

Run selection, installation, setting and annual checks straight down this table. Split protection is the heart of it: whichever branch carries whichever current is guarded by the relay set to that value, and any mismatch is protection running idle. Post the setting and measured values on the cabinet door for the next shift.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Thermal relay settings and trip characteristics follow GB/T 14048.4 (IEC 60947-4-1); overload protection principles refer to GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① A single thermal relay on the common circuit: one speed always runs under-protected and the winding pays for it
② Cross-wiring the thermal contacts: a low-speed trip locks out high speed and the whole machine idles
③ Class 10 relay on a long-start fan: the drive trips before the motor ever reaches speed

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.

Related reading