One contactor on a drawing consists of coil, main contacts and auxiliary contacts spread across different places. This page explains the full structure and how to reassemble it while reading.
The complete representation has three parts tied by one code: the coil (control-circuit rectangle labelled KM with its voltage), the main contacts (main circuit, one or three pairs labelled KM) and the auxiliary contacts (control circuit, several NO and NC labelled KM with suffixes). The three parts may sit on different sheets, but the letter code plus serial number regroups them into one device. Reading means following the code to reassemble the scattered parts into the complete contactor.
Main contacts sit in the main circuit carrying the motor current, annotated with the same code and often with the driven load noted beside them such as motor M1. The coil and auxiliary contacts sit in the control circuit, operated through buttons and other contacts. Auxiliary contact quantity determines self-holding, interlocking and signalling capability, and both style and quantity must match the hardware. When confused, reassemble the main and control sides under the KM code.
| Section | Position | Annotation | Function |
|---|---|---|---|
| Coil | control circuit | KM plus voltage | pick-up drive |
| Main contacts | main circuit | KM | switch the load current |
| NO auxiliary | control circuit | KM with suffix | self-holding, signalling |
| NC auxiliary | control circuit | KM with suffix | interlocking |
| Linkage | same code | KM plus number | reassemble the device |
A contactor comprises coil, main contacts and auxiliary contacts tied by one KM code scattered across the sheets; follow the code to reassemble the main and control sides into the complete device. Never draw main contacts as NC, never misstate the coil voltage, and keep the auxiliary count equal to the hardware.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Contactor symbols per GB/T 4728.7; selection per GB/T 14048.4 and IEC 60947-4. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.