The main breaker in a star-delta circuit must be set by delta running current, not detached from contactor rating. This article covers breaker rating, breaking capacity, grading with KM1/KM2, and motor protective breaker sizing to avoid failed or over-tripping protection.
Set the breaker by the delta running line current Ie, because the star start current is only about 0.33Ie, so rating follows steady state not starting. Choose a motor protective breaker with long-delay setting 1.0 to 1.1 Ie that rides through start yet trips on overload; too small trips at start, too large refuses to act.
The breaker breaking capacity Icu must exceed the prospective short-circuit current at its point. Grade the upstream breaker with KM1 so the upstream trips first and the contactor never clears the arc; contactors rated AC-3 cannot break short-circuit current, that job is the breaker's, and a small breaker can weld shut.
Do not fit a breaker on the star point side; overload protection belongs on the line-current side after KM1, or it trips at start. The KM3 star loop needs no breaker, only a small fuse or miniature breaker protects the control transformer, with the protection hierarchy set right.
| Device | Setting basis | Key | Note |
|---|---|---|---|
| Main breaker | steady Ie | MPCB 1.0-1.1Ie | watch Icu |
| Upstream breaker | fault current | grade below | trip first |
| KM1 | Ie×1.25 | AC-3 | no short break |
| Thermal | line side | set Ie | not star point |
| Ctrl MCB | xfmr | 2-6A | control short |
Rule: breaker by Ie, contactor by Ie×1.25, short-circuit by breaker, overload by line-side thermal. Grade top-down so the contactor never breaks short-circuit current, or it will weld and stick.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Breakers per IEC 60947-2, coordination per IEC 60947-4-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.