Coordination of circuit breaker and contactors in star-delta

The main breaker in a star-delta circuit must be set by delta running current, not detached from contactor rating. This article covers breaker rating, breaking capacity, grading with KM1/KM2, and motor protective breaker sizing to avoid failed or over-tripping protection.

1. How it works

Set the breaker by the delta running line current Ie, because the star start current is only about 0.33Ie, so rating follows steady state not starting. Choose a motor protective breaker with long-delay setting 1.0 to 1.1 Ie that rides through start yet trips on overload; too small trips at start, too large refuses to act.

2. Numbers and practice

The breaker breaking capacity Icu must exceed the prospective short-circuit current at its point. Grade the upstream breaker with KM1 so the upstream trips first and the contactor never clears the arc; contactors rated AC-3 cannot break short-circuit current, that job is the breaker's, and a small breaker can weld shut.

3. Pitfalls and fixes

Do not fit a breaker on the star point side; overload protection belongs on the line-current side after KM1, or it trips at start. The KM3 star loop needs no breaker, only a small fuse or miniature breaker protects the control transformer, with the protection hierarchy set right.

4. Star-delta breaker and contactor table

DeviceSetting basisKeyNote
Main breakersteady IeMPCB 1.0-1.1Iewatch Icu
Upstream breakerfault currentgrade belowtrip first
KM1Ie×1.25AC-3no short break
Thermalline sideset Ienot star point
Ctrl MCBxfmr2-6Acontrol short

5. Notes

Rule: breaker by Ie, contactor by Ie×1.25, short-circuit by breaker, overload by line-side thermal. Grade top-down so the contactor never breaks short-circuit current, or it will weld and stick.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Breakers per IEC 60947-2, coordination per IEC 60947-4-1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Never set breaker by start current.
② Never put thermal on star point.
③ Never let contactor break a fault.

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.