How AC contactors work and how to tell main from auxiliary contacts

The contactor is the heart of the control circuit, and misreading its terminals confuses everything. This page explains the electromagnetic principle and the shading ring, the terminal codes that separate main from auxiliary contacts, and how to read the nameplate ratings.

1. How it works

A contactor consists of an electromagnetic system, a contact system and arc chutes. Energizing the coil creates a field that pulls the armature in, closing the NO contacts and opening the NC ones; de-energizing releases it by spring. On AC the coil current alternates and the magnetic force passes through zero, which would chatter the armature, so the pole faces carry a shading ring whose induced current produces a force in quadrature, holding the armature through the zeros. A cracked shading ring announces itself as a loud hum with vibration, a useful field sign of ageing. Coils must pick up reliably between eighty-five and one hundred ten percent of rating; below that they hum or fail to seat.

2. Numbers and practice

Main contacts carry the motor current on the power circuit, three poles on thick terminals marked 1L1, 3L2, 5L3 on the supply side and 2T1, 4T2, 6T3 on the load side; the 18 in CJX2-1810 is the 18A main rating. Auxiliary contacts serve the control circuit, milliamps to a few amps, on thin terminals with two-digit codes, 13-14 for NO and 21-22 for NC, expandable with contact blocks to four plus four. Tell them apart with a multimeter: at rest, continuity marks NC and open marks NO, then hand-close the armature and re-measure, the flip confirms identification.

3. Pitfalls and fixes

Selection reads two nameplate keys: the rated working current under its utilization category and the coil voltage. AC-3 covers direct starting and breaking at speed; AC-4 covers jogging and plugging; AC-1 resistive loads. The same frame carries different currents per category, an 18A frame running a 7.5kW motor on AC-3 but only AC-4-class loads equivalent to a 9A frame under jogging. Read the code, CJX2-1810 means 18A mains with one NO auxiliary, coil voltage marked separately, then verify current against load, coil voltage against the control supply, and auxiliary count against the drawing before fitting.

4. Contactor contact identification reference

ItemMain contactsAuxiliary contactsIdentification
CircuitPower circuitControl circuitWire gauge and terminals
Terminal codes1L1/3L2/5L3 and 2T1/4T2/6T313-14, 21-22 and so onDigit codes
Current carriedMotor working currentmA to a few ampsAgainst nameplate
CountThree poles per setExpanded with blocksCount terminals
TimingFollow the coilFollow the coilHand-close and re-test
Failure signsErosion and weldingOxidized high resistanceMultimeter resistance

5. Notes

Use this table at new-panel acceptance and old-panel repair alike. The core is the terminal coding system: L/T codes for power, two-digit codes for control, and the rule that 1-2 means NC while 3-4 means NO, after which drawings and hardware stop being confusing.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Contactor requirements follow GB/T 14048.4 (IEC 60947-4-1); terminal identification and marking refer to GB/T 4026 and GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Auxiliary contacts carrying power-circuit load: the small contacts erode and weld and the control fails mid-run
② Ignoring a cracked shading ring: the hum and vibration wear the iron circuit until the armature jams
③ Sizing an AC-4 duty by the AC-3 frame: frequent jogging shrinks contact life and the unit dies early

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.