Paired quick reference of graphic symbols and letter codes

Recognising a graphic symbol is only half the job; each symbol must pair with the right letter code such as KM for contactors or QF for breakers. This page assembles the common pairings into one quick table for both reading and drafting.

1. How it works

A proper schematic pairs every device with a graphic symbol and a letter code: the graphic shows the shape, the code gives the identity. Usual families under GB/T 7159: Q for switching devices with QF breakers and QS disconnectors; F for protection with FU fuses, FR thermal relays and FV surge arresters; K for contactors and relays with KM, KA and KT; S for control switches with SB pushbuttons and SA selector switches; T for transformers with TC control transformers.

2. Numbers and practice

Within a family, subscripts and annotations do the sorting: KM1 and KM2 are two contactors; KT1 carries a delay mark with its setting such as 3s; SB1 with a NO symbol means start while SB2 with NC means stop. The graphics carry paired details too: a contactor coil with a mechanical-link mark implies its contact set, and a thermal relay draws both heating element and contact. When drafting, fix the letter code first and then draw; a symbol that contradicts its code is a beginner error.

3. Pitfalls and fixes

For an unfamiliar symbol, take three steps: outline first to pick the family, boxes being assemblies and contacts being switching devices; details next to pick the device, arc chutes marking main contacts and a stroke marking NC; then read the adjacent letter code and model, since the code is the final identity. When in doubt, open GB/T 4728 instead of guessing, because one mislabelled symbol propagates into wiring, purchasing and the BOM.

4. Paired graphic and letter codes for common devices

DeviceLetter codeGraphic featuresAction or use
Circuit breakerQFSwitch with X trip markOverload and short-circuit switching
DisconnectorQSSwitch with clear gapNo-load isolation, visible break
FuseFURectangle with centre lineOne-shot short-circuit protection
Thermal relayFRHeater plus contactOverload trip, auto reset
ContactorKMCoil plus arc-chute contactsFrequent load switching
Time relayKTCoil plus delay markDelayed contact output
PushbuttonSBNO or NC contactManual momentary control

5. Notes

Keep the table sorted by letter family in the drawing room and check every new drawing against it before issue. Companies may tune the codes, but one drawing set uses one convention, matched with the equipment ledger, BOM and terminal tags.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Letter codes per GB/T 7159; graphic symbols per GB/T 4728. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Pairing a symbol with the wrong code sends wiring and purchasing down the wrong identity and forces rework
② Inconsistent codes within one drawing set duplicate or drop BOM items and corrupt cost and material lists
③ Guessing between look-alike symbols mixes contactor and relay forms and breaks contact rating selection

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.