A strip must not run straight through; group by function and zone it so it is easy to find and maintain. This page covers how to group, mark and lay out terminal blocks.
Group terminals by loop function: power, control, signal and comms each form a block, separated by two or three spare holes or a barrier. Number each group continuously with non-overlapping ranges, so tracing means pick the group then the hole in three seconds. Label each group with a colour code. Trap: a mixed strip with no groups means half an hour hunting holes during a fault.
Lay strong and weak apart: power and control terminals on a separate row or zone from PLC and sensor terminals, with spare holes or a metal divider at least 50 mm apart. Put strong electric on top, weak on bottom, or left-right zones, and mark each group start with its name and range. Draw per-group pages so the fitter wires from the right page.
| Group | Content | Gap |
|---|---|---|
| Power | Incomer | Own row |
| Control | Relays | Spare |
| Signal | IO analogue | ≥50 mm |
| Comms | Bus | Metal |
| Earth | PE bar | Green |
| Label | No fade | Name |
Group the strip by function with continuous numbering and gaps or barriers between groups; keep strong and weak at least 50 mm apart. Label each group with a non-fading tag naming the group and range, draw per-group pages, update labels on change and verify by group at acceptance.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electrical documentation per GB/T 6988, terminal marking per GB/T 4026, terminals per IEC 60947-7-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.