An undersized contactor welds, an oversized one wastes money. This page gives the sizing basis chain for a two-speed panel, from nameplate currents through utilization categories to make-and-break checks, and walks one complete worked example.
The sizing chain runs nameplate current, utilization category, margin factor, then verification. Record the line current of each speed separately: constant-power machines draw more at high speed, constant-torque machines more at low speed, and each branch sizes its own contactor, KM1 or KM2, never one figure for both. Category: cage-motor direct starting with breaking at speed is AC-3; frequent jogging and plugging is AC-4. Two-speed changeover sits in AC-3 territory, but KM1 breaks the loaded low-speed current at every switch, so verify the AC-3 breaking rating. Margin: 1.1 to 1.2 for normal duty, 1.3 for frequent changeover or hot cabinets.
Worked example: a YD200L four-pole and two-pole motor rated 18.5kW at 35A in low-speed delta and 22kW at 42A in high-speed double star. KM1: 35A on AC-3 with 1.1 margin, take a 40A frame. KM2: 42A with margin, take a 50A frame. KM3: neutral-point current is near zero in steady state, but by the matched-contact principle take the same 50A frame as KM2 for spares commonality. Verify making capacity, which AC-3 requires at eight times rated working current against a starting current of six to seven times rating; verify KM1 breaking 35A under load. Short-circuit withstand belongs to the breaker and thermal relays, not the contactor.
Special conditions: above forty degrees derate five to ten percent per the maker curve; above 2000m altitude derate and check contact temperature rise; dense mounting below fifty-millimeter spacing wants a 1.05 to 1.1 upscale; above 300 operations per hour verify mechanical and electrical life and choose heavy-duty types. The two-speed peculiarity: on machines switching more than ten times per hour, KM1 breaks loaded current every time, so contact wear concentrates there, set the maintenance interval by KM1 and stock spares double. Write nameplate currents, category, margin and verification conclusions on the selection sheet.
| Step | Content | Value | Check |
|---|---|---|---|
| Nameplate currents | Record each speed | Example 35A / 42A | Match to KM1 and KM2 |
| Utilization category | Starting and breaking duty | Mainly AC-3 | Frequent jogging raises to AC-4 |
| Margin factor | Normally 1.1~1.2 | 1.3 for frequent changeover | Adjust for harsh environment |
| Frame selection | Round up to standard | 40A / 50A | KM3 matches KM2 contacts |
| Making capacity | At least 8 times rating | Start at 6~7 times rating | Within range |
| Special conditions | Temperature, altitude, density | Derate 5%~10% | Per maker curve |
Six steps with values and checks, and the completed table is a full selection record. The iron rule is branch-by-branch sizing plus category correction; the biggest mistakes are one rating for both speeds and ignoring that KM1 breaks loaded current at every changeover.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Contactor utilization categories and rated working currents follow GB/T 14048.4 (IEC 60947-4-1); motor ratings and starting-current characteristics refer to GB/T 755. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.