Use and cautions of jumpers on terminal blocks

A jumper links several terminals into one bus; used well it saves wire, used wrong it burns equipment. This page covers how to choose, fit and avoid pitfalls with jumpers.

1. How it works

The jumper (bridge joins adjacent equipotential terminals, e.g. merging several 24 V positives into one common bus instead of wiring them pairwise. Types are fixed (maker-supplied, spans 2 to 10 positions) and plug-in (breakable for service). Its current rating must equal or exceed the linked wire, typically 20 to 40 A. Trap: a thin jumper on a high-current main melts and takes a whole section with it.

2. Practice and pitfalls

Fit only across equipotential terminals, never bridge different loops like 24 V and 0 V; confirm equal potential with a meter first. Plug-in jumpers get an insulated cap when open. For high current parallel several and sum the rating, or use a copper bar. The jumper must align with the terminal row or it sits loose. To measure current, open the jumper and insert the meter, then refit exactly.

3. Jumper usage rules

ItemRequireWrong
BridgeEquipotentialShort trip
Rating≥WireMelt
FitSeat fullyLoose arc
OpenIns capMistouch
ReplaceNo messHard find
MarkRed tagWrong pull

4. Notes

Bridge only equipotential terminals with rating at least the wire (20 to 40 A), confirm with a meter and seat fully. Cap plug-in jumpers when open, never replace with loose wire. Separate potentials with a spare hole or barrier, red-tag key jumpers against wrong removal, and periodically check for looseness and discolouration.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electrical documentation per GB/T 6988, terminals per IEC 60947-7-1, marking per GB/T 4026. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Jumper across different loops: short trip on power
② Half-seated jumper: loose and arcs
③ Loose wire instead of jumper: messy hard to find

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.