The reference designation is the key to finding a component on site. A disciplined scheme lets a fitter walk to the right cabinet tag and straight to the target; a sloppy one turns the plant into a maze. Here are the habits and rules.
The component designation per GB/T 5094 answers which one and what class; the position number answers where it is mounted. One component is KM1 by designation and plus C12 by position, meaning cabinet C position 12. You read the designation on the schematic and use the position tag to find the hardware; the two are bound together in the parts list. Position numbers usually follow the mounting unit such as cabinet, box or panel plus a sequence.
Common habits: inside a cabinet use row and column coordinates such as C12 for cabinet C row one column two, and tag the component there; number terminal blocks by block and point such as X1:1 and X1:2; number PLC rack modules by slot such as rack0 slot3; draw a layout on the panel door so position matches the drawing; on cross cabinet wires mark source and target positions for clear traceability. Tag with durable labels and verify position against drawing before run.
| Item | Do | Example |
|---|---|---|
| Designation | Which and class | KM1 |
| Position | Where mounted | +C12 |
| In cabinet | Row column | C12 |
| Terminal | Block dot | X1:1 |
| PLC | Slot | rack0 slot3 |
| Bound | List matches | Drawing hardware |
Rule: the designation answers which one per GB/T 5094, the position answers where; read designation on drawing, find by position tag on site, and bind the two in the list. Use row column inside cabinets, block dot for terminals, slot for PLC, keep layout matching coordinates, and verify position against drawing before run.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Position identification per GB/T 5094 (IEC 61346), symbols per GB/T 4728, documentation per GB/T 6988. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.