Fuse and circuit breaker symbols with their rating annotations

Fuses and circuit breakers both provide short-circuit protection but their symbols and behaviour differ completely. This page shows how each is drawn, what ratings to annotate, and why the two must never be interchanged on a drawing.

1. How it works

A fuse (FU) is a rectangle with a slanted wavy line inside for the fusible element. It protects by melting once, so it must be replaced after every operation. Annotate the fuse-link current such as 63A and the breaking capacity such as 50kA. Fuses sit in main circuits or on the primary of control transformers for short-circuit protection; keep the wavy line consistent so nobody mistakes it for a resistor.

2. Practice and pitfalls

A circuit breaker (QF) is a square box with an X or fork mark indicating the automatic tripping mechanism. It switches loads manually, trips automatically, and resets for reuse. Annotate frame current, trip curve class C or D, and breaking capacity. The essential difference: the breaker resets and handles load switching with a defined trip curve, while the fuse is cheap and single-shot. A box with an X is a breaker, a rectangle with a wave is a fuse, and the two symbols are never interchangeable.

3. Fuse and circuit breaker symbol comparison table

DeviceSymbolLetter codeMarking points
Fusewavy line in rectangleFUlink current, breaking capacity
Circuit breakerX in square boxQFframe current, trip curve
Isolatorknife symbolQSisolation only, no protection
Load switchknife plus arcQLload switching allowed
Fuse-switchknife plus waveQFUisolation plus fusing

4. Notes

The inner mark separates the two devices: a wavy line means fuse, an X in a box means breaker. Their protection characteristics differ, so never mix them up, and breaking capacity plus trip curve must be annotated or selection errors turn into equipment damage.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Protective device symbols per GB/T 4728.7; selection and breaking capacity per GB/T 14048 and IEC 60947 series. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Breaker drawn as a fuse: load switching becomes impossible and purchasing is misled
② Breaking capacity not annotated: a breaker explodes when short-circuit current exceeds its rating
③ Fuse drawn like a resistor: readers misjudge it as a current-limiting resistor

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.