When the strip drawing spills onto a second page, unclear cross-page marks break the wiring on site. This page covers page references, interruption symbols and continuous numbering.
Mark cross-page links with an interruption symbol at the page edge plus the destination page and position, e.g. P3/A5. When one strip spans two pages, draw half a terminal at each edge with paired page references so the reader flips and continues. EPLAN pairs cross-page references automatically; hand drawings must state page and row-column at both ends, or the chain breaks.
Numbering must stay continuous across pages: page one ends at X1:20, page two continues from X1:21, never restart. Bridges across pages carry the bridge number and partner page at the edge. Head each page with the total and the page span (strip X1, 60 holes, this page 1 to 30). Trap: two pages both starting at 1 lets the fitter wire hole 1 twice and short the circuit on power-up.
| Item | Marking | Check |
|---|---|---|
| Interrupt | Edge break | Both ends |
| Page ref | P3/A5 style | Paired |
| Numbering | Continuous | No restart |
| Bridge | No. plus page | Matches |
| Header | Total span | Read first |
| Checklist | Row by row | Briefing |
Use edge interruption symbols with paired page and position references, keep strip numbering continuous across pages and head each page with its span. Verify with a cross-page checklist row by row, brief the fitters on the joints, and prefer a landing terminal over flying lines.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Documents per GB/T 6988, symbols per GB/T 4728. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.