Drawing review is not a rubber stamp: main circuits are checked for capacity and protection, control circuits for logic and interlocks. This page lists the checkpoints for both sides so a review follows the list instead of the mood.
Review the main circuit on five points. Capacity: wire size and breaker settings match the motor current, verified by computing rated current against the device list. Protection: overload and short-circuit tiers complete, a thermal relay on every motor branch. Isolation: a maintenance isolator with visible break, control tapped downstream. Phasing: rotation and reversal swap points marked. Earthing: motor frames bonded to PE from the earth zone. Tick each point against its spot on the sheet.
Review the control circuit on six points. Supply: control voltage and transformer rating stated. Logic: start, hold-in and stop correct when simulated step by step. Interlocks: reversing contactors mutually locked, guard and e-stop chains in series with paired NC contacts. Contact duty: no contact carries more than its rating. Numbering: wire and terminal numbers match the terminal schedule. Signalling: lamps reflect true states. Write every contradiction into the review minutes.
Run the review in three stages: self-review by the designer with the checklist, cross-review by a second engineer focused on logic simulation, and final approval by the supervisor. Grade the findings: class A logic errors force a redraw, class B missing annotations get a deadline, class C suggestions are optional. After revision, re-review and close each finding one by one; only a fully closed set becomes the construction issue, and the minutes become the baseline for future changes.
| Object | Checkpoint | Method | Pass criterion |
|---|---|---|---|
| Main capacity | Wires match settings | Compute rated current | 1.2x margin on devices |
| Protection tiers | Overload and short complete | Per-branch check | Thermal relay per motor |
| Control logic | Start and stop correct | Simulate the sequence | Matches the process |
| Interlocks | Reversal and e-stop in place | Check paired NC contacts | Cannot be bypassed |
| Numbering | Wire list consistency | Spot check ten points | Drawing, hardware, table agree |
| Review closure | Findings cleared | Minutes item by item | Class A and B all closed |
Turn the checklist into a template so review quality stops depending on personal experience. Feed typical errors into a company mistake library and read it before new designs; the same errors stop repeating and reviews get faster with use.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Review requirements per the design verification clauses of GB/T 5226.1; drawing quality per GB/T 6988.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.