Interlock requirements for bidirectional star-delta switching

Some equipment like hoists needs bidirectional run after star-delta start, where switching is complex and interlock demand is high. This article covers multiple interlocks among forward/reverse and star/delta contactors, sequence constraints and safety.

1. How it works

Bidirectional run needs forward KM_F and reverse KM_R interlocked (NC series), the baseline. On top sit the star-delta KM2/KM3 interlock and the constraint between them: only after stable delta full-voltage may forward/reverse switch; reversing during star or mid-switch is forbidden or it surges. Verify all four contactor interlock wires one by one.

2. Numbers and practice

Safe sequence: star-delta finishes start into delta full voltage, runs steady, only then KM_F/KM_R may act to reverse. On reverse, open the current direction contactor first, after a dead band close the opposite, and reversing is only allowed in delta. Wire a KM2 NO as the permit-reverse condition in series with KM_F/KM_R coils, logically locking reversal during star.

3. Pitfalls and fixes

Add mechanical interlock on the forward/reverse contactors against electrical sticking. Commission with lamps per beat: during star neither KM_F nor KM_R may energize, after stable delta either may act, reverse is break-before-make. Power restore after outage must reset in order to prevent auto-start; post warning tags on site.

4. Bidirectional star-delta interlock table

PairWireEffectFail
KM_F-KM_RNC seriesno simultaneousphase short
KM2-KM3NC seriesno simultaneousphase short
Star no reverseKM2 NO in F/Rlock reversesurge
Reverse dead bandbreak-makeno arcweld
Mech lockcontactor bodydoublestick fail

5. Notes

Rule: forward/reverse interlock at base, star-delta interlock saves life, KM2 NO as permit-reverse, reverse break-before-make with dead band. Verify all four interlocks with lamps; wire rather redundant than missing, one miss shorts.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Interlocks per IEC 60947-4-1, safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Skip forward/reverse interlock, short.
② Allow reverse in star, surge.
③ Reverse make-before-break, weld.

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.