MOULDLKnowledge BaseElectrical Knowledge Base3D Model DownloadsMembership
中文版Model Store »
Knowledge Base › Electrical Knowledge Base › Component designation naming rules in EPLAN
HomeModels
Table of contents

On this page

Electrical Control & Drawings (500 articles)

Quick Reference

Component designation naming rules in EPLAN

EPLAN does not hand draw schematics; it binds designation, device data, terminals and wire numbers inside a database. A loose naming scheme makes the auto generated reports and BOM a mess. Here are the naming rules and good habits in EPLAN.

1. How it works

EPLAN combines project structure (higher level code =, location code +) with the component designation such as KM1 into a full device identity. In the device navigator every component carries designation, type, parameters and macro. Suggestion: first set the structure in project settings such as =A for power and +C for cabinet, then assign designations to components, keeping consistent with GB/T 5094 and avoiding ad hoc numbers.

2. Practice and pitfalls

Good habits: use the device identifier such as KM rather than free text so later filtering works; fill model and specification into the part master data so the BOM carries them automatically; number terminals by block and point such as X1:1 and use plug definitions for connectors; use interrupt points for cross sheet links so the system associates by code; agree upper or lower case across the team and lock it, no personal style.

3. EPLAN naming table

ElementDoUse
Structure=A +CSplit sys loc
IdentifierKM not textEasy filter
MasterFill modelBOM carries
TerminalX1:1Standard
InterruptCross linkAutomatic
CaseUnified lockNo mix

4. Notes

Rule: in EPLAN set the project structure first (=A system, +C location), then assign designations consistent with GB/T 5094; use device identifiers not free text, unify case, fill the part master so the BOM carries the model, use interrupt points across sheets, and run a report check before output.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Project structure per GB/T 5094 (IEC 61346), documentation per GB/T 6988, EPLAN practice follows IEC 61346 reference designation. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Free text for code: report cannot filter it
② Mixed case KM1 and km1: treated as two
③ No master data: BOM has code but no model

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.

Related reading

Related 3D models: Ready to build it? Download free 3D models & CAD drawings at MOULDL »
MOULDL · Electrical Knowledge Base · free self-study reference for electrical & automation engineers, 3D CAD models at MOULDL