EPLAN does not hand draw schematics; it binds designation, device data, terminals and wire numbers inside a database. A loose naming scheme makes the auto generated reports and BOM a mess. Here are the naming rules and good habits in EPLAN.
EPLAN combines project structure (higher level code =, location code +) with the component designation such as KM1 into a full device identity. In the device navigator every component carries designation, type, parameters and macro. Suggestion: first set the structure in project settings such as =A for power and +C for cabinet, then assign designations to components, keeping consistent with GB/T 5094 and avoiding ad hoc numbers.
Good habits: use the device identifier such as KM rather than free text so later filtering works; fill model and specification into the part master data so the BOM carries them automatically; number terminals by block and point such as X1:1 and use plug definitions for connectors; use interrupt points for cross sheet links so the system associates by code; agree upper or lower case across the team and lock it, no personal style.
| Element | Do | Use |
|---|---|---|
| Structure | =A +C | Split sys loc |
| Identifier | KM not text | Easy filter |
| Master | Fill model | BOM carries |
| Terminal | X1:1 | Standard |
| Interrupt | Cross link | Automatic |
| Case | Unified lock | No mix |
Rule: in EPLAN set the project structure first (=A system, +C location), then assign designations consistent with GB/T 5094; use device identifiers not free text, unify case, fill the part master so the BOM carries the model, use interrupt points across sheets, and run a report check before output.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Project structure per GB/T 5094 (IEC 61346), documentation per GB/T 6988, EPLAN practice follows IEC 61346 reference designation. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.