When to add an intermediate relay in a jog loop

Driving the contactor coil straight from the button is fine, but once you need multi-point control, a signal to PLC, or a long button wire, add an intermediate relay KA. This page tells which scenes need it and why.

1. How it works

The intermediate relay KA has several contacts, moderate rating and low coil power, used to amplify and convert signals. In a jog loop: with a remote button and long wire drop, the button drives only small-current KA, which then drives the contactor on short thick wire; one button controlling several devices uses KA contacts to expand; sending a jog-active state to a lamp, PLC input or alarm, KA contacts give clean passive contacts; and it isolates weak button from strong power for safety.

2. Practice and pitfalls

Wire SB to KA coil, KA NO contact replaces the button to feed KM coil, no latch so hold-to-run. Other KA contacts go to a lamp, a PLC input X, or a buzzer. Match KA coil voltage to supply (24 V DC or 220 V AC common) and its contact rating to the load, but never the motor main circuit (5 to 10 A only). In PLC retrofit KA is a great passive isolator feeding the input.

3. Intermediate relay use

SceneRoleWire
Remote btnlow currentSB drives KA
Multi ptexpandKA pairs
To PLCpassivecontact to X
Lampstatuscontact lit
Isolateweak/strongSB weak
Pitmain loadweld

4. Notes

Add KA in jog loops for remote buttons with drop, one button to many devices, passive contacts to PLC or lamp, and weak-strong isolation. KA contact in series with KM coil gives jog, spare contacts expand status. Match voltage and never let KA carry the main circuit.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Control relay GB/T 14048 with IEC 60947; PLC GB/T 15969. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① KA on main: contacts weld
② Wrong coil volt: burn
③ No number: messy fix

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.