The electrical layout and the mechanical drawing are drawn separately, but cabinet parts must land on the punched holes or they will not fit. This page shows how to align the two and avoid rework.
The mechanical structure drawing (general assembly shows frame, mounting plate, door and cut-outs in millimetres, defining the physical envelope. The electrical layout projects breakers, PLC, terminal blocks and drives on the plate with centre coordinates and spacing. Both must share one projection system and origin, or the overlay misaligns. The structure shapes the cabinet; the layout places the parts.
Coordination step one is to overlay and check: each component outline (e.g. a 100×120 mm breaker) must sit fully inside the plate or cut-out with at least 10 mm wiring clearance. Step two, one common origin at the plate corner, tolerance ±1 mm. Step three, spacing for heat: drives need ≥100 mm above and below for airflow, hot parts away from capacitors, ≥50 mm between power and signal. Traps: a cut-out 2 mm small that will not accept the part, or a transformer on the door back that blocks closing.
| Check item | Structure | Layout |
|---|---|---|
| Outline | Outline size | Centre coord |
| Cut-out | Outline+2 mm | Within bounds |
| Spacing | Plate strength | Wiring ≥10 mm |
| Door gap | Hinge pos | Projection ≥5 mm |
| Origin | 0,0 corner | Same ±1 mm |
| Airflow | Vent | Drive ≥100 mm |
Keep one coordinate system and one origin; overlay both drawings and verify before punching. Any change must update both, or the door will not close. Add an interference layer projecting all protruding parts onto the door interior, and reconcile the BOM.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drawing practice per GB/T 6988, symbols per GB/T 4728, structuring per IEC 61346. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.