MOULDLKnowledge BaseElectrical Knowledge Base3D Model DownloadsMembership
中文版Model Store »
Knowledge Base › Electrical Knowledge Base › How the electrical layout drawing works with the mechanical structure drawing
HomeModels
Table of contents

On this page

Electrical Control & Drawings (500 articles)

Quick Reference

How the electrical layout drawing works with the mechanical structure drawing

The electrical layout and the mechanical drawing are drawn separately, but cabinet parts must land on the punched holes or they will not fit. This page shows how to align the two and avoid rework.

1. How it works

The mechanical structure drawing (general assembly shows frame, mounting plate, door and cut-outs in millimetres, defining the physical envelope. The electrical layout projects breakers, PLC, terminal blocks and drives on the plate with centre coordinates and spacing. Both must share one projection system and origin, or the overlay misaligns. The structure shapes the cabinet; the layout places the parts.

2. Practice and pitfalls

Coordination step one is to overlay and check: each component outline (e.g. a 100×120 mm breaker) must sit fully inside the plate or cut-out with at least 10 mm wiring clearance. Step two, one common origin at the plate corner, tolerance ±1 mm. Step three, spacing for heat: drives need ≥100 mm above and below for airflow, hot parts away from capacitors, ≥50 mm between power and signal. Traps: a cut-out 2 mm small that will not accept the part, or a transformer on the door back that blocks closing.

3. Layout versus structure checklist

Check itemStructureLayout
OutlineOutline sizeCentre coord
Cut-outOutline+2 mmWithin bounds
SpacingPlate strengthWiring ≥10 mm
Door gapHinge posProjection ≥5 mm
Origin0,0 cornerSame ±1 mm
AirflowVentDrive ≥100 mm

4. Notes

Keep one coordinate system and one origin; overlay both drawings and verify before punching. Any change must update both, or the door will not close. Add an interference layer projecting all protruding parts onto the door interior, and reconcile the BOM.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drawing practice per GB/T 6988, symbols per GB/T 4728, structuring per IEC 61346. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Cut-out 2 mm smaller than part will not fit
② Changing layout only leaves door blocked or terminals hitting door
③ Mismatched origins overlay misaligns parts from holes

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.

Related reading

Related 3D models: Ready to build it? Download free 3D models & CAD drawings at MOULDL »
MOULDL · Electrical Knowledge Base · free self-study reference for electrical & automation engineers, 3D CAD models at MOULDL