A component designation is not a random name; it has a class (a letter by function group) and a hierarchy (system, location, class, terminal). Clear class and hierarchy make reading, BOM and cross system tracing smooth. Here is the method.
Classification picks the letter from the GB/T 5094 function group: energy E, supply G, conversion U, motor M, switching Q, contactor relay K, measuring P, protection F, signal H, terminal X, transformer T, resistor capacitor C. Set the class letter first, then sequence within the class. A consistently classified drawing tells you K is control and F is protection at a glance, no table needed.
Hierarchy uses four segments: higher level code (=A for system) plus location code (+C for mount) plus class code (K for type) plus terminal code (:1 for point). A simple device may drop higher and location, keeping only class plus number (KM1); a complex plant uses all four as =A+C-KM1 for cross system uniqueness. Number by first drawing system boundaries, then mount zones, then sequential within each zone; clear layers, easy trace.
| Layer | Meaning | Example |
|---|---|---|
| Class | Function letter | K/M/F |
| Higher | Split system | =A/=B |
| Location | Split mount | +C |
| Kind | Element type | KM1 |
| Terminal | Point | :1 |
| Simplified | Small gear | KM1 only |
Rule: classify first by function (energy, switch, protection, measure, signal, terminal, actuation), then layer higher (system) plus location (mount) plus class (element). Simple gear may drop layers to class only; big systems keep all three as =A+C-KM1, sequential within zones for easy trace.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Code classification and layering per GB/T 5094 (IEC 61346), documentation per GB/T 6988, symbols per GB/T 4728. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.