Reversing needs only two phases swapped, but which two and where the cross sits are often unclear to beginners. This article explains the phase-sequence principle, why the third phase must stay untouched, and why the cross must sit on the load side of the contactor, with wiring options compared.
A three-phase system has only two sequence states, forward and reverse. Swapping all three lines returns to the original sequence and the motor does not reverse; swapping any two reverses it. Hence crossing L1 with L2, L2 with L3 or L1 with L3 all give identical results. Site practice prefers crossing L1 and L3, the two outer phases, keeping the middle phase as a fixed reference so the wiring and the drawing both read cleanly.
The cross must sit on the load side of KM2, between its outgoing terminals and the overload relay or motor. Crossing on the supply side leaves the parallel busbars with poor clearance and invites phase-to-phase shorts during maintenance. With the cross on the load side both contactors see the same sequence on their supply side, and only KM2 has two load-side phases crossed, which keeps the circuit easy to read and to test. The third phase must never be crossed: an odd number of swaps on both branches makes both buttons drive the same direction, and metallic cross-connection between the two branches can bolt two phases together. Check phasing before the first start.
| Option | Phases swapped | Third phase | Result |
|---|---|---|---|
| Outer phases | L1 and L3 | L2 direct | Reverse (common) |
| L1 with L2 | L1 and L2 | L3 direct | Reverse |
| L2 with L3 | L2 and L3 | L1 direct | Reverse |
| All three crossed | All | None | No reversal (wrong) |
| Cross on load side | KM2 load side | Untouched | Correct practice |
| Cross on supply side | KM2 supply side | Untouched | Short risk (forbidden) |
The rule: swap two phases only, keep the third untouched, cross on the load side. Jog on first power-up to confirm the two buttons give opposite rotation before any continuous running.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB 50052 for power supply and distribution, GB 14048.4 for low-voltage apparatus, IEC 60947-4 and IEC 60204-1 for reference. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.