Interlock and limit interlock design in reciprocating control

In reciprocating control, the forward-reverse interlock and limit interlock are two life-saving gates; omit one and you get short circuit or crash. This note explains electrical interlock, mechanical interlock and limit interlock and how they combine, plus common omissions and miswires in design.

1. How it works

The forward and reverse contactors must interlock electrically: the forward auxiliary NC series in the reverse coil branch and vice versa, so one pulled in opens the other coil, preventing both main contacts closing and shorting the supply. This is the basic interlock, and omitting it is the most common design error. Use the contactor own auxiliary NC, not another relay, or action is unsynchronised.

2. Practice and pitfalls

For critical duty add mechanical interlock on the contactors besides electrical, blocking simultaneous close even if contacts weld, double insurance. Limit interlock is the travel switch NC in the direction branch, cutting that direction at end, motion protection. Division: electrical prevents short, mechanical prevents welded same-close, limit prevents overrun. Draw all three in the diagram and test each at acceptance. Common omissions: limit interlock forgotten so no stop at end; swap NO not paralleled to reverse start so only stops not swaps. Wrong: limit as NO series runs away on break; interlock using the other start button auxiliary instead of contactor auxiliary reverses logic. After design, push every state through a truth table before build.

3. Interlock design sheet

TypePartWirePrevents
ElectricalAux NCSeries coilSame short
MechanicalLatchBlockWeld same
LimitLimit NCIn dirOverrun
SwapLimit NOPar revStop no swap
OmitMiss oneAddTest
WrongNO seriesNCBreak run

4. Notes

Three life-saving gates: electrical interlock prevents same-close short, mechanical prevents welded same-close, limit prevents overrun. Draw all three, swap NO parallels reverse start, push every state through a truth table before build, test each at acceptance.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Interlock safety per GB/T 5226.1 chapter 9, IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① No limit interlock: crash
② Wrong interlock contact: same close
③ Stop no swap: NO not par

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.