An undersized control transformer sags when several coils pick up together, and wrong secondary voltages shorten component life. This page covers the capacity calculation, how to allocate multiple secondary windings, and the grounding and fuse design that make the control supply bulletproof.
Size for pickup, not for holding: a contactor draws five to eight times its holding VA at pickup, and simultaneous pickups stack. The expression runs S at least K times the summed pickup VA plus the summed holding VA plus other loads, with K equal to one for simultaneous whole-line restarts and 0.3 to 0.5 for staggered sequenced starts. Worked example: five contactors summing 330VA pickup, timers and relays holding 23VA, lamps 8VA; the simultaneous case needs about 380VA, take 400VA; the staggered case about 180VA, take 250VA. Keep chronic loading under eighty percent, since a full transformer ages fast, and then verify the voltage drop: the pickup instant must stay above eighty-five percent of rating including cable drop.
Configure secondary voltages on safety and compatibility: ordinary control at 220V or 110V, where 110V lengthens lamp and contact life and suits imported equipment; wet or operator-facing circuits at safety voltage 36V or 24V; PLC inputs and electronics on 24V DC from a separate switching supply, isolated from AC. One transformer may carry several secondary windings, one for control, one for lighting, one for indication, each with its own fuse so faults stay local. Ground one secondary terminal and fuse the live side, a single-phase-to-earth protection design. Mark voltage levels on terminal blocks and distinguish circuits by color or wire gauge against mixing.
Grounding and protection: the grounded secondary turns an earth fault into a fuse operation instead of a sustained arc, the essence of the safety design, with earth conductor at least 2.5mm² to the PE bar. Fusing: primary at 1.5 to 2 times transformer rating, each secondary branch independently at 1.2 to 1.5 times its load. Accept by measuring no-load secondary voltages within five percent of nameplate, running the pickup simulation with all contactors hand-closed and holding the dip under fifteen percent, and a two-hour full-load heat run within temperature-rise limits. Track secondary voltage quarterly; a downward trend reveals ageing windings or creeping load.
| Item | Value or practice | Basis | Check method |
|---|---|---|---|
| Rated capacity | By summed pickup VA | Worst simultaneous case | Voltage-drop test |
| Loading | Under 80% long term | Temperature-rise life | Heat run |
| Secondary voltages | Control at 220/110V | Safety plus compatibility | No-load measurement |
| Safety voltage circuits | 36V or 24V | Wet or operator zones | Against drawing |
| Secondary grounding | One end earthed, 2.5mm² minimum | Single-fault protection | Earth continuity test |
| Fusing | Primary 1.5~2 times | Independent per branch | Ratings verified |
Six configuration points run selection, installation and acceptance. The control transformer is the heart of the panel supply: capacity from the worst simultaneous pickup, voltages from safety and compatibility, grounding and fusing from single-fault protection; get those three right and the control power stays trouble-free for a decade.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Control supply requirements follow GB/T 5226.1; transformer technology refers to the GB/T 1094 series. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.