Sequential start is easy, sequential stop (front may not stop until rear stops) is harder to wire. This article wires both: start permitted by front NO, stop blocked by rear NO, with a two-motor example.
Start circuit: SB2_1 starts KM1 with self-hold; KM1 NO is in series with the KM2 start, so only after KM1 pulls in can SB2_2 start KM2. This hard-constrains 1 then 2. Each stop button is at the front of its own branch, independent of rear, press which to stop which (rear stopped while front runs is normal).
Sequential stop needs rear-not-stopped blocks front-stop. Wire the rear (KM2) NO contact to bypass or hold the front (KM1) stop condition, so while KM2 runs it shorts KM1 stop; KM2 must stop before KM1 can. Stop also cascades, releasing back to front.
Start interlock: front NO to rear start (front-to-back); stop interlock: rear NO to front hold (back-to-front). Opposite directions form full order start front-to-back, stop back-to-front. After wiring verify with lamps: KM1 stop is ineffective while KM2 runs, KM1 stops only after KM2 stops.
| Stage | Start inter | Stop inter |
|---|---|---|
| Cascade | front NO in rear | rear NO lock front |
| Button | self+stop each | stop independent |
| E-stop | total front | all stop must |
| Verify | lamp order | per beat |
| Example | two motors | basic |
Rule: start front NO in rear, stop rear NO lock front, opposite directions. After wiring lamp-test: KM1 stop ineffective while KM2 runs, KM1 stops after KM2 stops.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Wiring per GB/T 4728, safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.