Main circuit versus control circuit in electrical schematics

On a machine-tool schematic, the thick lines running to the motor form the main circuit and the thin logic web that commands the contactor is the control circuit. This page draws the line between the two, explains the dividing rules and how they interact.

1. How it works

The main circuit is the power path to the load: from the supply through the breaker, contactor main contacts and thermal relay to the motor, carrying amps, drawn thick on the left or top. The control circuit is the signal web deciding when the main circuit closes: pushbuttons, relay contacts and contactor coils, carrying fractions of an amp, drawn thin on the right or bottom. The quick test is at both ends: a run touching the supply or motor is main, a run ending on control devices is control.

2. Numbers and practice

Division is about duty as well as weight: the main circuit converts and distributes energy, the control circuit judges logic and provides interlock, protection and signalling. Voltages differ too: mains at AC380V/220V versus control at AC220V, 110V, 48V or DC24V, so the control transformer marks the boundary. Numbering follows suit, mains zones 1, 2, 3 and control zones from 101, letting readers segment the sheet before tracing.

3. Pitfalls and fixes

The two circuits are master and servant: any contact change in the thin web moves the contactor in the thick path, so start, stop and reversal are all decided by the control side. Fault-finding differs accordingly: heat and insulation on the main path, logic and contacts on the control side. The classic trap is replacing the contactor because it does not pull in, when a corroded auxiliary relay contact in the control loop was the real culprit.

4. Main versus control circuit quick comparison

AspectMain circuitControl circuitReading point
FunctionPower distribution and driveLogic and interlockingSplit main and control first
Current levelA few amps to hundredsUsually under 5AThick versus thin lines
Typical voltageAC380V/220VAC220V/110V/DC24VNote the control transformer
Sheet positionLeft or topRight or bottomSame rule for landscape
Line widthThick, 0.5mm and upThin, 0.25mmKeep 2:1 ratio
Key devicesQF, KM, FR, MSB, KA, KT, HLZone by numbering

5. Notes

Splitting the two circuits is step one of reading any schematic: locate motors and contactor main contacts, then pushbuttons and coils, and the backbone is clear. During troubleshooting attack the two sides separately and you save half the time.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Division and drafting of main and control circuits per GB/T 6988.1; symbols per GB/T 4728. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Checking only the main circuit leads to swapping healthy contactors while the fault is a corroded control contact
② Mixing control and main voltage levels burns a 220V coil instantly when fed 380V
③ Unlabelled zoning of the two circuits makes handover and training slow and error-prone

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.