Installation drawings look simple, but one wrong hole or routing detail and the site cannot mount or it overheats. This page covers the details that trip designers up.
Door and plate cut-outs must use the real outline plus 2~3 mm clearance and avoid stiffeners and studs. VFD and servo cut-outs need cooling air (≥100 mm clear above and below) or heat is trapped. Button holes must match panel thickness with long nuts if thick. Traps: a hole on a stiffener cants the part; a display hole smaller than the screen will not seat. Mark every hole centre and ±0.5 mm tolerance.
Route strong and weak wiring apart, ≥50 mm or a metal divider; fill trunking under 70% or later wires cannot be pulled. Number both ends per GB/T 6988. Keep the earth bar separate, protective and signal earth joined only at one point. Traps: a stuffed trunk cannot be reworked; random earth splices cause interference and earth-leakage trips. The drawing must show trunk size, route and fixings.
| Detail | Requirement | If wrong |
|---|---|---|
| Hole margin | Outline+2~3 mm | Will not fit |
| Cooling | ≥100 mm gap | Overheat |
| Strong/weak | ≥50 mm | Noise |
| Trunk fill | ≤70% | Hard pull |
| Access | ≥30 mm | Hard serv |
Cut-outs use real outline plus 2~3 mm and avoid stiffeners; VFDs keep ≥100 mm air above and below. Keep strong/weak ≥50 mm apart or divided, trunk fill ≤70%. Separate earth bars, one-point earth. Reserve 20% spare terminals and 15% spare conduit, and ≥30 mm working space.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Documents per GB/T 6988, symbols per GB/T 4728, safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.