Star-delta starting connects the motor windings in star during start to cut voltage and current to about one third, then switches to delta for full-voltage running. This article explains the voltage relation, the current and torque reduction, and the contactor switching sequence.
In delta running each winding sees the full line voltage. In star starting the winding ends are tied together so each phase only sees the phase voltage, line voltage divided by square root of three, about 58 percent. That lower voltage is what limits the starting current.
The start current in star is roughly one third of a direct delta start, and the start torque drops with the square of the voltage to about one third. The method therefore fits light or no load starts such as fans and pumps, not heavy belts.
Three contactors do the job: main, star and delta. At start main and star pull in, then after a set delay the timer drops star and closes delta. A break before make gap prevents a phase to phase short.
| Parameter | Star start | Delta run |
|---|---|---|
| Winding voltage | 0.577 times line | Equal to line |
| Start current | About 1/3 direct | High inrush |
| Start torque | About 1/3 full | Full torque |
| Suitable load | Light or no load | Rated load |
| Switch time | 4 to 15 s | n/a |
| Typical power | 11 to 75 kW | same |
Rule: use star-delta only for light load, use a soft starter or autotransformer for heavy load. Set the changeover delay by load inertia: 5 to 8 s for pumps, 8 to 12 s for compressors.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Design follows GB/T 5226.1 and IEC 60204-1 for electrical safety. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.