When a star-delta motor stops mid-way after start, the switch has failed. This article follows the symptom tree of start-runs-star, no-delta, stops-on-switch to locate KT, KM3, KM2 and interlock, with step-by-step checks.
If the motor runs in star but never switches, KM1, KM3 and supply are fine and the fault is in switching. Check that KT is energized and timing; a worn pneumatic diaphragm or wrong electronic setting stops it, so KM2 never pulls in and the motor just runs low-voltage (speed will not rise). A burnt KT coil or reversed contact also blocks the switch.
If it stops the moment it switches, KM3 released but KM2 did not take over. Check whether the KM2 coil is energized (is the interlock locking it out), whether KM2 main contacts are burnt open, and whether KM2 NC interlock wrongly locks itself. The bridge may also be drawn reversed so delta never closes and the motor loses power and stops.
If the breaker trips at switch, there is a switch-time short, usually KM2 and KM3 closing together (missing interlock) or a reversed KM2 bridge. De-energized, check the NC series is complete and that like phases conduct when KM2 pulls in; also a too-short KT dead band lets the two overlap and arc.
| Symptom | Points to | Check | Fix |
|---|---|---|---|
| Star no delta | KT dead | KT lamp | swap KT |
| Stops on switch | KM2 no take | KM2 coil | interlock contact |
| Trip on switch | switch short | like-phase | interlock bridge |
| Low speed | stuck star | KT NO | contact |
| Loose star | noise | tighten | re-crimp |
Rule: star-no-delta checks KT, stops-on-switch checks KM2 and interlock, trip-on-switch checks short and bridge. Use a clamp meter to see whether current jumps from star to delta at switch; no jump means KM2 never engaged.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Protection per IEC 60947-5, safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.