Knowledge Base › Electrical Knowledge Base › Troubleshooting star-delta switch failure that stops the motor
HomeModels
Table of contents

On this page

Electrical Control & Drawings (500 articles)

Quick Reference

Troubleshooting star-delta switch failure that stops the motor

When a star-delta motor stops mid-way after start, the switch has failed. This article follows the symptom tree of start-runs-star, no-delta, stops-on-switch to locate KT, KM3, KM2 and interlock, with step-by-step checks.

1. How it works

If the motor runs in star but never switches, KM1, KM3 and supply are fine and the fault is in switching. Check that KT is energized and timing; a worn pneumatic diaphragm or wrong electronic setting stops it, so KM2 never pulls in and the motor just runs low-voltage (speed will not rise). A burnt KT coil or reversed contact also blocks the switch.

2. Numbers and practice

If it stops the moment it switches, KM3 released but KM2 did not take over. Check whether the KM2 coil is energized (is the interlock locking it out), whether KM2 main contacts are burnt open, and whether KM2 NC interlock wrongly locks itself. The bridge may also be drawn reversed so delta never closes and the motor loses power and stops.

3. Pitfalls and fixes

If the breaker trips at switch, there is a switch-time short, usually KM2 and KM3 closing together (missing interlock) or a reversed KM2 bridge. De-energized, check the NC series is complete and that like phases conduct when KM2 pulls in; also a too-short KT dead band lets the two overlap and arc.

4. Star-delta switch-fail symptom table

SymptomPoints toCheckFix
Star no deltaKT deadKT lampswap KT
Stops on switchKM2 no takeKM2 coilinterlock contact
Trip on switchswitch shortlike-phaseinterlock bridge
Low speedstuck starKT NOcontact
Loose starnoisetightenre-crimp

5. Notes

Rule: star-no-delta checks KT, stops-on-switch checks KM2 and interlock, trip-on-switch checks short and bridge. Use a clamp meter to see whether current jumps from star to delta at switch; no jump means KM2 never engaged.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Protection per IEC 60947-5, safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Tune KT but ignore interlock.
② Skip KM2 main contacts check.
③ Skip interlock on trip, short stays.

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.