Someone thought wiring a contactor contact across the jog button would let it also hold, but instead it runs continuously and jog fails. This page analyses the exact behaviour after paralleling a latch there.
Normal jog: button SB NO in series with KM coil, press to close release to open. If you parallel a KM auxiliary NO (latch) across SB, pressing SB pulls KM and the aux also closes; after releasing SB the current reroutes through the parallel KM aux to the coil, so it stays energized and runs continuously. In effect the loop becomes a latching (run) circuit and the jog is locked into continuous run.
Behaviour: first press KM pulls and motor turns, normal; release SB and it should stop, but the closed aux keeps the coil fed so the motor keeps running, jog becomes run; you cannot stop by releasing, you need the stop button or power off; without a stop button it runs until overload or power loss. Paralleling a latch onto a jog button is redundant and kills the jog.
| Action | Should | Actual |
|---|---|---|
| Press | run | run |
| Release | stop | keeps run |
| Press again | run | already |
| Stop by | release | need stop |
| Nature | jog | becomes run |
| Conclusion | no parallel | cut hold |
After paralleling a latch across the jog button, releasing SB reroutes current through the KM aux to keep the coil, jog becomes run and release will not stop it. That wrongly turns jog into continuous run. To combine jog and run use the jog button NC to cut the hold, not a parallel latch. Remember jog means no holding.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage devices GB/T 14048 with IEC 60947; safety GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.