Fans and pumps run for long periods, so they almost always use latching (run) control. This page covers the typical application and cautions.
Fans and pumps run continuously, so after a start press the KM pulls, its auxiliary self-holds and the motor keeps running until stop is pressed. Compared with jog, latching frees the operator from holding the button and suits unattended or remote control. One latch loop per fan or pump in the panel keeps the structure clear and easy to maintain.
Wire supply to breaker to KM main to thermal to motor; control has NC stop, NO start across KM aux, coil, thermal NC. Fans and pumps also take differential or level switches for auto start-stop, these series into the loop or feed the PLC. For star-delta or soft-start, the latch still comes from the run contactor. Protection must include overload, short circuit and phase-loss.
| Device | Control | Protect |
|---|---|---|
| Fan | run | overload |
| Pump | run | phase |
| Auto | level diff | series |
| Big I | star-delta | run latch |
| Maint | test latch | clean |
| Auto-on | special | el1131 |
Fans and pumps use latching run control with overload, short and phase-loss protection, and auto start-stop by level or differential. No auto-recovery after blackout is a safety feature; a restart design is needed only for exhaust that must resume. Keep a local hard e-stop.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Safety GB/T 5226.1 with IEC 60204-1; motor GB/T 12350. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.