Sequential start faults cluster in three types: no start, wrong order, false stop. This article gives a cause tree and steps per symptom, covering buttons, interlock wires, KT and thermals, with a quick table.
If no stage starts on any button, first check control transformer L1L2, whether the total E-stop has reset, and whether the main breaker tripped. When this common link is down nothing moves; confirm total and control power, then check each stage.
If a rear stage (KM2) starts without the front or in wrong order, the front interlock NO is likely missing or miswired, or the rear start button is shorted. Verify the front KM1 NO is truly in series with KM2 start; use an ohmmeter on the interlock wire. Wrong order means a cascade break is misplaced.
A stage stopping mid-run may be thermal mis-trip, a stop button whose NC opened from damp, or a poor interlock NO contact dropping the rear. De-energized check thermal setting and contacts, tighten terminals; add anti-vibration and contact monitoring where vibration is high. Isolate stage by stage to locate fastest.
| Symptom | Cause | Check | Fix |
|---|---|---|---|
| All no start | total power/E-stop | measure L1L2 | reset |
| Rear runs wild | front interlock miss | NO series | add series |
| Wrong order | cascade break | trace wire | rewire |
| False stop | thermal/stop btn | setting contact | tighten |
| KT no time | coil/type | lamp | swap |
| No reverse | rear lock miss | NO | add lock |
Rule: all-no-start checks total power and E-stop, rear-wild checks front interlock, false-stop checks thermal and stop button, no-reverse checks rear NO lock. Isolate stage by stage with instruments, do not guess.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Faults per IEC 60947-5, safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.