MOULDLKnowledge BaseElectrical Knowledge Base3D Model DownloadsMembership
中文版Model Store »
Knowledge Base › Electrical Knowledge Base › Voltage rating and insulation requirements of terminal blocks
HomeModels
Table of contents

On this page

Electrical Control & Drawings (500 articles)

Quick Reference

Voltage rating and insulation requirements of terminal blocks

Besides current, a terminal carries a rated insulation voltage; selecting by current only and putting a 250 V class block on a 380 V loop is a hidden hazard. This page explains the markings and verification.

1. How it works

A terminal nameplate shows two key voltages: the rated insulation voltage Ui (insulation design basis, commonly 250, 400 or 690 V) and the rated working voltage Ue (allowed circuit voltage, affected by pollution degree and creepage). The same block allows less working voltage at pollution degree 3 than at degree 2. Selection must ensure Ue is at least the highest loop voltage; a 380/400 V cabinet picks at least the 400 V class, and drive outputs need margin for voltage spikes.

2. Practice and pitfalls

Withstanding voltage is really creepage and clearance: the distances between adjacent terminals and from terminal to rail set the withstand. A 690 V class UK block has at least 5.5 mm creepage between neighbours. Do not mix different voltage classes on one strip without spare holes or barriers, and check the insulating body for cracks before fitting. Acceptance: 2500 V mains for 1 s without breakdown, or a 500 V megger reading over 1 megohm on control circuits.

3. Withstand and insulation table

ItemRuleVerify
Ui≥1.5x loopNameplate
Ue≥real voltagePollution
Creepage≥5.5 mm/690 VCaliper
Mixed rowsGap or barrierVisual
Withstand2500 V/1 sTest
Insulation≥1 MΩMegger

4. Notes

Check Ui and Ue before selecting: 400 V class minimum for a 400 V cabinet with spike margin on drive outputs. Verify creepage by voltage class, never mix voltage classes without isolation. Accept with 2500 V for 1 s, control circuits at 500 V megger over 1 megohm, and retest in damp seasons.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Terminals per IEC 60947-7-1, assemblies per GB/T 7251.1, insulation per GB/T 16935.1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① 250 V class on a 380 V loop breaks down
② Mixed voltages without barrier shorts
③ Cracked insulation fails the test

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.

Related reading

Related 3D models: Ready to build it? Download free 3D models & CAD drawings at MOULDL »
MOULDL · Electrical Knowledge Base · free self-study reference for electrical & automation engineers, 3D CAD models at MOULDL