The sleeve says 101, the strip says 12: what does each identify and how do they cooperate? This page explains the division of labour and the mapping between the two.
Wire number and terminal number live on different axes: the wire number identifies one conductor and travels with it, the same at both ends; the terminal number identifies one hole on a fixed strip. One wire runs from hole 12 to hole 7 with 101 on it throughout. They pair through the wiring diagram rows (wire number plus start terminal plus end terminal) and the strip drawing (hole plus wire number), so tracing locks the wire by number and the hole by position.
The mapping lives in the wiring diagram and wire table: each table row holds the wire number, start (device tag plus terminal) and end (device tag plus terminal), and each strip hole names its wire number. Query both ways: wire to holes, hole to wire. EPLAN keeps the map automatically; hand drawings need the three documents (schematic, wiring, strip) checked consistent. Trap: wire numbers without terminal references leave you holding a wire with nowhere to land. Field routine: look up 101, get KA2:9 to X1:12, verify the sleeve at hole 12, then meter the path; change the hole and the wire number stays, change the wire and the terminal stays, change both and update table, drawing and sleeves together.
| Object | Identifies | Trait |
|---|---|---|
| Wire no | One conductor | Travels, same ends |
| Term no | One hole | Fixed on strip |
| Wiring doc | The mapping | Number plus ends |
| Wire table | Two-way query | Number to hole |
| Hole change | Wire same | Update table |
| Wire change | Hole same | Update sleeve |
Wire numbers travel with conductors, terminal numbers stay with holes; the wiring diagram and wire table map one to the other both ways. Trace by table, verify at the strip, confirm with a meter. Changing a hole keeps the wire number, changing a wire keeps the terminal, and changing both updates table, drawing and sleeves together.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Documents per GB/T 6988, terminal marking per GB/T 4026, wires per IEC 61175. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.