Real drawings accumulate all kinds of symbol errors, most of them basic ones. This page collects the highest-frequency mistakes with their corrections so a review can tick them off one by one.
The top mistake is swapping NO and NC, which turns self-holding into interlocking and stop into start. The correction: drawings show the de-energised rest state, NO open and NC closed, and every contact is traced through pick-up before release. Mistake two: an emergency stop drawn without its hexagon frame fails the safety review, so the hexagon is mandatory. Mistake three: an auxiliary contact labelled with another device code breaks the self-holding loop, so one device keeps one code with suffixes.
Mistake four: a breaker graphic labelled FU, so the buyer orders fuses; graphic and code must agree. Mistake five: a solenoid valve drawn with contacts like a relay when it only has a coil; the electrical sheet shows the coil only and the valve paths go on the fluid drawing. Mistake six: a thermal relay contact drawn NO, so the contactor never holds in; draw it NC. Mistake seven: a CT secondary drawn as openable, a latent high-voltage hazard; mark never-open and earth it.
| Mistake | Consequence | Correction | Review point |
|---|---|---|---|
| Contacts swapped | self-holding becomes interlocking | draw the de-energised state | trace every point |
| Emergency stop without frame | fails safety review | add the hexagon | check the frame |
| Graphic contradicts code | wrong device purchased | align code and graphic | check material list |
| CT drawn openable | high-voltage hazard | mark never-open | check the secondary |
| Thermal relay drawn NO | motor never starts | draw NC | check the contact |
Review with a checklist covering the emergency-stop frame, contact states, code consistency, earth continuity and the CT never-open rule. Mark revisions in red with the old symbol crossed and the new one circled, and update the material list and terminal list at the same time, or the drawing and the hardware still disagree.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Symbol correctness per GB/T 4728 and the review requirements of GB/T 6988; safety aspects per GB 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.