Configuring phase-failure protectors in star-delta circuits

A star-delta motor on open phase burns its winding fast. This article covers selection and wiring of the phase-failure protector, where to sample, whether it sits in main or control circuit, with field configuration tips.

1. How it works

The phase-failure protector should monitor the motor's real supply phases, best taken as line current or voltage after the motor terminals U1V1W1. Because terminal phase identity does not change across the star-delta switch, sampling after KM1 and before the motor is most accurate; do not monitor only the supply incoming, or a loss after KM1 is missed. Current transformers around the three motor leads are most reliable.

2. Numbers and practice

On detecting any missing phase or unbalance beyond threshold, the protector opens its NC contact after a delay (usually 1 to 3 s to ride through the switch transient), de-energizing KM1 and stopping the motor. Wire the contact in series with the KM1 coil or KT coil so phase loss stops the machine. Choose voltage or current type correctly and match the operating voltage and contact rating to the control circuit.

3. Pitfalls and fixes

Phase protector, thermal and breaker form three layers: breaker for short-circuit, thermal for overload, protector specifically for phase loss and unbalance, none replacing another. The line-side thermal in star-delta already reflects phase loss, but a dedicated protector reacts faster. Commission by pulling one phase to simulate loss and confirming timely stop.

4. Star-delta phase-loss config table

ItemChoiceKeyNote
Samplemotor end after KM1most exact
Typecurrent XFMRaround 3 leads
Delay1-3 sride switch
OutputNC in KM1 coilstop on loss
Layerwith thermal breakerno replace
Testpull phaseverify stop

5. Notes

Rule: sample at motor end, output in KM1 coil, delay to ride the switch, three layers each doing its job. After install, pull one phase to test; timely stop proves it works, do not wait for a real fault.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Motor protection per IEC 60947-4-1, safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Sample only the incoming supply, misses loss.
② Parallel output, phase loss no stop.
③ Confuse with thermal relay, wrong layer.

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.