How to draw a terminal-strip drawing and its order

The terminal-strip drawing is not drawn at random; list first, place holes, then mark numbers. Wrong order means rework. This page gives the standard method and sequence.

1. How it works

The sequence is: first the component list to fix which wires and loops connect; then place terminals in a row on the drawing, separating strong and weak zones; then mark each hole with its terminal number, component code and wire number; last draw jumpers and earth marks. Do not reverse it. Use EPLAN or CAD with separate layers for holes, numbers and bridges. Trap: drawing without a list then finding the loop count wrong halfway.

2. Practice and pitfalls

Draw a front developed view: terminals in a row, number below each hole and wire number above. Double-level terminals use A/B and offset. Jumpers are thick lines joining bridged holes with spec noted. Earth terminals sit at the ends marked PE. The border notes model, rail and total holes. Keep 1 to 2 mm gaps and uniform number direction toward the reader.

3. Terminal drawing sequence

StepContentOutput
1 ListLoops and wiresWire list
2 PlaceZone orderHole layout
3 MarkNumber wireNumber layer
4 BridgeJump earthBridge layer
5 LinkThree matchChecklist
6 VerifyHole vs realArchive

4. Notes

Draw in the order list, place, mark, bridge, link and verify; separate zones and uniform number direction. Keep the strip drawing, wiring and schematic numbers in agreement, checking wire ends and terminal destinations. Provide a spare-hole list and verify hole by hole against the real strip before archiving.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electrical documentation per GB/T 6988, terminal marking per GB/T 4026, terminals per IEC 60947-7-1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Drawing without list: loop count wrong rework
② Non-uniform number direction: wired reversed
③ Three drawings mismatch: tracing all wrong

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.

Related reading