Inside a control cabinet there can be hundreds of wires. Without proper wire numbers and labels, fault finding turns into a needle-in-a-haystack job and rewiring mistakes become likely. This article explains the requirements and practice for wire markers and component labels so that every wire is traceable to the drawings.

1. How it works

Wire markers matter because each conductor must correspond to a terminal on the schematic and wiring diagram. The standard practice is to fit a heat-shrink or PVC marker on both ends of every wire, with the wire number assigned by equipotential principle. Clear and durable marking is a mandatory acceptance item and missing markers can fail inspection.

2. Numbers and practice

Printing and mounting requirements: use a dedicated wire-marking machine to print heat-shrink or PVC sleeves with a font height of at least 3 mm, white-on-black or black-on-yellow, containing the wire number and terminal number. Sleeves are fitted on both ends oriented for easy reading, and each core of a multi-core cable is numbered independently. Terminal blocks carry tags with the component code matching the drawings, and critical circuits use colour coding.

3. Pitfalls and fixes

Common mistakes: fitting a marker on only one end leaves the other end bare and still hard to trace. Numbers not assigned by equipotential make drawings impossible to follow. Always sleeve both ends, number per drawing, use durable heat-shrink, and tag terminals with codes.

4. Wire Marker Requirements Quick Table

ItemRequirementCheck
MarkerBoth endsTraceable
Font>=3mm clearDurable
Wire no.EquipotentialMatch drawing
Terminal tagCode labelConsistent
ColourFunction codePrevent error

5. Notes

Wire numbering and labelling is a mandatory acceptance item for control cabinets. Sleeve both ends, number per equipotential, use durable heat-shrink, and tag terminals with codes. Verify every marker against the drawings before delivery.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Conductor marking see GB/T 4884, indicators see GB/T 4025 (IEC 60073), electrical drawings see GB/T 6988, machine safety see GB/T 5226.1 (IEC 60204-1). Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Marker on one end only: other end bare still hard to trace
② Numbers not equipotential: drawings impossible to follow
③ Handwritten peeling markers: blur over time

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.