Are contacts drawn energised or not? Can symbols be rotated? These old questions get wrong answers every week. This page answers the frequent ones and lists the five most common symbol mistakes seen on factory drawings.
Under GB/T 4728, symbols show the de-energised, unoperated state: contactor contacts are drawn normally open, pushbuttons unpressed, limit switches untripped. The reading rule follows: what the picture shows has nothing to do with the live state, so logic must be traced through the control circuit. Common answers: drawing a NO contact as NC is not a drafting fault but reverses all logic; symbols may be rotated or mirrored but not into something unrecognisable; and one drawing set never mixes two symbol systems.
Five mistakes come up again and again: drawing a thermal relay with a breaker symbol although their protective duties differ; omitting the stroke across an NC contact so crews wire it as NO; mixing main and auxiliary contactor symbols although main contacts carry the arc-quenching form for load current; using one earth symbol for PE and N in a TN-S system, which fails inspection; and leaving pilot lamp colours unmarked so installers choose red and green themselves.
Give symbol questions a home: keep a Q&A log, let anyone register a dispute, and each quarter roll the agreed answers into the company convention page so every department answers the same way. Put the frequent disputes into the title block notes of new drawings, and train newcomers with real cases from the log rather than by reciting clauses; within six months drawing disputes drop noticeably.
| Question | Correct answer | Basis | Site impact |
|---|---|---|---|
| State shown by symbols | De-energised, unoperated | GB/T 4728 custom | Logic must be traced |
| NO/NC drawn reversed | Drafting fine, logic reversed | State convention | Control acts opposite to intent |
| May symbols rotate | Yes, rotate or mirror | Meaning unchanged | Never beyond recognition |
| Main vs auxiliary contacts | Main use arc-chute form | Different ratings | Mixing misleads sizing |
| PE and N symbols | Draw protective earth apart | TN-S requirement | Mixed symbols fail inspection |
| Pilot lamp colours | Must be marked on drawing | Company rule | Otherwise installers choose |
Most symbol mistakes trace back to forgetting the static-state convention; teach that one rule first and half the errors vanish. Print the quick table for the drawing room and keep the dispute log growing into a company casebook.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Symbol state and drafting conventions per GB/T 4728; protective earthing per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.