Maintenance wants manual jogging, production wants automatic sequential starting, and the two modes must never overlap. This page shows how a single selector switch separates the two circuits cleanly — contact grouping, mode exclusion and where the automatic chain hangs.
Use a two- or three-position selector SA. Manual position feeds individual start, stop and jog branches for each motor; automatic position feeds a timer chain where KM1 starts KT1, KT1 closes KA1 after 10 s to pick KM2, and KM2 starts KT2 which releases KM3 after another 8 s. The two branches are mutually exclusive on the switch; only thermal NCs and the main stop stay common, so nothing crosses during changeover.
The automatic chain is a straight signal line: any failed link stops the sequence exactly there, which makes fault location trivial. The manual branch bypasses the whole chain, so a maintenance jog is not dragged through the delays. Color-code the two branches on the drawing — blue for manual, red for automatic — and print each KT setting on the print.
Mode switching only at standstill: turning SA while running drops every contactor and rebuilds seals in the new mode, a shock to belts and gears. Prefer a zero-position guard or a mechanical detent so SA cannot be turned while running. If a thermal trips in automatic, the line stops in reverse order; switch to manual to reset and diagnose unit by unit.
| Aspect | Manual mode | Automatic mode |
|---|---|---|
| Selector | SA manual position | SA automatic position |
| Starting | independent buttons | one button, KT cascade |
| Jogging | supported for setup | not available |
| Cascade | optional, for tests | KT and KA strictly enforced |
| Use case | repair and trials | normal production |
Change KT settings on the drawing first, then on the dial, and rerun the full-chain check so paper and panel stay identical. Keep the mode rule visible at the panel: no switching under load.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Manual and automatic operation per GB/T 5226.1, symbols per GB/T 4728. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.