A row of buttons and lamps on the control panel is meaningless without codes; SB is button, HL is lamp, and you must also tell normally open from closed and red from green. Here is how to code pushbuttons and indicators on the drawing.
Buttons use S (control switch class), with SB as pushbutton and SA as selector switch; indicators use H (signal class), with HL as indicator lamp and HA as buzzer. Contact nature is told by suffix or note: normally open NO, normally closed NC. Number by function group: one group for emergency stop, one for start stop, one for run indication, sequenced inside the group, for example SB1 emergency stop, SB2 start, SB3 stop.
Panel to drawing: on the panel layout mark each button or lamp with its code and silk text such as SB2 start, and keep silk and code identical; on the schematic draw the NO or NC contact and label it SB2 with NO or NC noted; beside HL note colour and meaning (green run, red fault, yellow pre warning); bind the PLC input address to the button code (SB2 to a DI address), recorded in the IO table. Once tagged, nameplate, drawing and PLC must agree. For multiple stations number by segment (station 1 SB11-19, station 2 SB21-29).
| Device | Letter | Example |
|---|---|---|
| Button | SB | SB1/SB2 |
| Selector | SA | SA1 |
| Lamp | HL | HL1 |
| Buzzer | HA | HA1 |
| Contact | NO/NC | Noted |
| Multi station | Segment | SB11-19 |
Rule: button SB, selector SA, lamp HL, buzzer HA, number by function group in sequence (SB1 stop, SB2 start, SB3 stop); keep panel silk identical to code, mark contact NO or NC, note lamp colour and meaning, bind PLC address in the IO table, and segment across stations (station 1 SB11-19, station 2 SB21-29).
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Component letter codes per GB/T 5094 (IEC 61346), symbols per GB/T 4728, documentation per GB/T 6988. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.