Realizing jog and latch in one circuit

A machine may need both continuous run (latch) and micro jog from one circuit. This page explains the classic jog-plus-run combined circuit done with one selector or one special button.

1. How it works

Latching uses a self-hold: start button SB2 parallels a KM auxiliary NO contact, so after press the contactor stays energized. Jog breaks that hold: the jog button SB3 carries a NC contact in series with the latch, and when pressed it first opens the latch while its NO contact feeds the coil, so hold-to-run release-to-stop with the self-hold forced off. Both share one coil without conflict.

2. Practice and pitfalls

Three ways: two-button, where SB2 starts with latch and SB3 jogs with its NC cutting the latch; single-button using a NO plus NC button that switches jog and run by pressing (el-1108); or a selector SA choosing jog or run and opening the latch in jog. Always confirm the jog NC really cuts the latch, or jog turns into run.

3. Jog plus run combined

FuncPartWire
RunSB2+KM auxparallel hold
JogSB3 NCcut hold
Jog onSB3 NOseries coil
SingleNO+NC btnswitch
SelectSA poschoose
PitNO onlyjog becomes run

4. Notes

Combine jog and run with one contactor: run parallels the auxiliary for self-hold, jog uses the button NC to cut the hold while its NO feeds the coil. Pick among two-button, single-button or selector. Test by ear that jog truly cuts the hold; do not let jog become run.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage devices GB/T 14048 with IEC 60947; safety GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Jog NO only: stays latched as run
② Self-hold on main: messy logic
③ Unclear positions: wrong operation

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.

Related reading

Related 3D models: Ready to build it? Download free 3D models & CAD drawings at MOULDL »
MOULDL · Electrical Knowledge Base · free self-study reference for electrical & automation engineers, 3D CAD models at MOULDL