A machine may need both continuous run (latch) and micro jog from one circuit. This page explains the classic jog-plus-run combined circuit done with one selector or one special button.
Latching uses a self-hold: start button SB2 parallels a KM auxiliary NO contact, so after press the contactor stays energized. Jog breaks that hold: the jog button SB3 carries a NC contact in series with the latch, and when pressed it first opens the latch while its NO contact feeds the coil, so hold-to-run release-to-stop with the self-hold forced off. Both share one coil without conflict.
Three ways: two-button, where SB2 starts with latch and SB3 jogs with its NC cutting the latch; single-button using a NO plus NC button that switches jog and run by pressing (el-1108); or a selector SA choosing jog or run and opening the latch in jog. Always confirm the jog NC really cuts the latch, or jog turns into run.
| Func | Part | Wire |
|---|---|---|
| Run | SB2+KM aux | parallel hold |
| Jog | SB3 NC | cut hold |
| Jog on | SB3 NO | series coil |
| Single | NO+NC btn | switch |
| Select | SA pos | choose |
| Pit | NO only | jog becomes run |
Combine jog and run with one contactor: run parallels the auxiliary for self-hold, jog uses the button NC to cut the hold while its NO feeds the coil. Pick among two-button, single-button or selector. Test by ear that jog truly cuts the hold; do not let jog become run.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage devices GB/T 14048 with IEC 60947; safety GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.