Hydraulic, pneumatic and electrical drawings often share one folder but obey different symbol systems: fluid power shows flow paths, electricity shows contacts and coils. This page separates the three systems and nails down the interface between them.
Fluid power symbols follow GB/T 786.1 and describe flow paths: boxes stand for valve positions, arrows for flow direction, T-blocks for blocked ports, with energy from pumps or compressors. Electrical symbols follow GB/T 4728 and describe circuits: contacts, coils, terminals. The same solenoid appears as a drive mark on the end of a valve in the fluid diagram and as coil YV1 in the electrical schematic, so one electro-hydraulic machine puts every solenoid valve on two drawings with two meanings.
Align the interface through letter codes: when YV1 energises in the schematic, the electromagnet shifts the valve position in the hydraulic diagram and the directional valve in the pneumatic one. The convention is one tag on both drawings, each cross-referencing the other by page. Pressure and flow belong on the fluid sheets, voltage and interlocks on the electrical ones; never squeeze hydraulic parameters into the electrical title block, or reviewers face two sets of numbers that disagree.
The cross-diagram trap is sequence. Give every cycle a sequence table with four aligned columns: step, electrical devices energised, valve positions, actuator motion. Commissioning then ticks the table cell by cell: if a solenoid does not shift, first check coil power in the electrical sheet, then pressure in the fluid sheet; responsibilities stay clean. Without such a table, debugging depends on one veteran memory and restarts with every new person.
| Aspect | Hydraulic/pneumatic | Electrical | Interface rule |
|---|---|---|---|
| Governing standard | GB/T 786.1 | GB/T 4728 | Declare both on page one |
| Content shown | Valve positions and flow | Contacts, coils, terminals | Each draws its own |
| Solenoid drawing | Drive mark at valve end | Coil symbol YV | Same tag on both |
| Parameters | MPa, L/min | V, A | Never cross title blocks |
| Motion expression | Box switching | Contact logic traced | Aligned by sequence table |
| Cross reference | See electrical pages | See fluid pages | Marked mutually |
A fixed order helps: electrical schematic first, fluid diagrams in the middle, sequence table at the back, so a reader flows through one binder. Matching tags across drawings is a hard rule; mismatched numbers double fault-finding time.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Fluid power symbols per GB/T 786.1; electrical symbols per GB/T 4728. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.