Practical use of auxiliary relays in sequential starting circuits

The auxiliary relay KA is the universal helper of the control circuit: it extends contacts, isolates signals, latches states and relays small outputs. This page gives four typical uses and the selection rules that keep the panel tidy and reliable.

1. How it works

Contact extension: when a contactor offers only one NO and one NC, a KA coil paralleled with it lends three NOs for cascade, pilot lamps and remote signalling. Isolation: a PLC or electronic output drives the KA coil, and KA contacts switch the 220 V contactor coil. Memory: a self-holding KA latches a fault state until the reset button clears it. Relaying: big control loops are switched through KA so only thin wires reach the pushbutton box.

2. Numbers and practice

Select by three things. Coil voltage must equal the control voltage, commonly 220 V AC or 24 V DC, mind polarity on DC. Contact rating: use full nameplate value for resistive loads, derate for inductive coils — a 10 A relay should drive at most two or three 220 V contactor coils. Count contacts with one spare; a JZ7-44 gives four NO and four NC, an HH52P octal plug-in gives two changeovers.

3. Pitfalls and fixes

On-site habits: give each KA one NO to light a panel lamp so run, interlock and fault states are readable at a glance; fit a 0.1µF plus 100Ω snubber across contacts that switch coils; number wires by function block so the drawing matches the cabinet; and periodically measure contact drop — above 0.2 V, schedule replacement.

4. Auxiliary relay uses and quick selection

UseWiring keyTypical choice
Contact extensionKA coil parallels KM, lends contactsJZ7-44, 4 NO + 4 NC
Signal isolationsmall front contact drives KA, KA drives loadHH52P socket type, 24 V DC
State memoryKA NO self-holds through reset buttonsmall plug-in relay
Cascade relayfront KA NO in series with rear coilcontacts = stages + 1
Lamp driverKA NO lights the panel lamprating 2x lamp current

5. Notes

Keep two spare relays of each type in the panel. Before swapping, verify coil voltage and socket wiring; on vibrating machines glue the relay body to stop contact chatter.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Relay requirements per GB/T 14598 series, control design per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Wrong coil voltage, 380 V bought for a 220 V circuit: chattering or burnout, always check the nameplate first
② No snubber across coil-switching contacts: erosion and welding, fit 0.1µF plus 100Ω across the contact
③ Relays packed with no spacing: heat stacks and shortens life, leave one relay-width gap in dense panels

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.