The auxiliary relay KA is the universal helper of the control circuit: it extends contacts, isolates signals, latches states and relays small outputs. This page gives four typical uses and the selection rules that keep the panel tidy and reliable.
Contact extension: when a contactor offers only one NO and one NC, a KA coil paralleled with it lends three NOs for cascade, pilot lamps and remote signalling. Isolation: a PLC or electronic output drives the KA coil, and KA contacts switch the 220 V contactor coil. Memory: a self-holding KA latches a fault state until the reset button clears it. Relaying: big control loops are switched through KA so only thin wires reach the pushbutton box.
Select by three things. Coil voltage must equal the control voltage, commonly 220 V AC or 24 V DC, mind polarity on DC. Contact rating: use full nameplate value for resistive loads, derate for inductive coils — a 10 A relay should drive at most two or three 220 V contactor coils. Count contacts with one spare; a JZ7-44 gives four NO and four NC, an HH52P octal plug-in gives two changeovers.
On-site habits: give each KA one NO to light a panel lamp so run, interlock and fault states are readable at a glance; fit a 0.1µF plus 100Ω snubber across contacts that switch coils; number wires by function block so the drawing matches the cabinet; and periodically measure contact drop — above 0.2 V, schedule replacement.
| Use | Wiring key | Typical choice |
|---|---|---|
| Contact extension | KA coil parallels KM, lends contacts | JZ7-44, 4 NO + 4 NC |
| Signal isolation | small front contact drives KA, KA drives load | HH52P socket type, 24 V DC |
| State memory | KA NO self-holds through reset button | small plug-in relay |
| Cascade relay | front KA NO in series with rear coil | contacts = stages + 1 |
| Lamp driver | KA NO lights the panel lamp | rating 2x lamp current |
Keep two spare relays of each type in the panel. Before swapping, verify coil voltage and socket wiring; on vibrating machines glue the relay body to stop contact chatter.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Relay requirements per GB/T 14598 series, control design per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.