Where to place the stop button in series in a latch line

The position of the stop button in the latch loop decides whether it can actually stop the motor. This page covers the key wiring points and wrong placements.

1. How it works

Standard: the supply first passes the stop button (NC) then splits to the start branch and the KM auxiliary (latch) branch, both to the coil. The stop sits at the front of the common feed, so pressing it cuts the whole control loop including the latch, dropping the contactor. This position stops the motor whether or not the latch is built.

2. Practice and pitfalls

Wrong placements: stop only in the start branch leaves the latch fed so the motor will not stop; stop after the latch point makes it start-priority where a held stop is bypassed; one stop of several wired parallel instead of series fails. The stop must be series and before every hold path. On PLC, put the stop first in logic and keep a hard-wired e-stop.

3. Stop button position

PositionEffectVerdict
Feed topcuts allright
Start onlylatch livewrong
After latchstart pririsk
Stops pardeadwrong
E-stophard cutadd
Testcut dropscheck

4. Notes

Place the stop button in series at the front of the common feed, covering both start and latch branches. Wrong placement leaves the motor running or makes start-priority. Series multiple stops, hard-cut the e-stop, and test by wire-cut and by holding stop plus start.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Safety GB/T 5226.1 with IEC 60204-1; buttons JIS C 4520. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Start branch only: latch stays
② After latch: start-priority
③ Stops parallel: one dead

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.