Thermal protection in a coordinated circuit is more than one relay per motor; the stopping range is the design core. This page covers per-machine protection, how downstream machines follow an upstream trip, and how alarms and resets are managed.
Every machine gets its own thermal relay at the contactor outlet, set to its own nameplate current, with the NC contact in series with its own coil circuit. That is the per-machine layer. Choose the relay by each motor rated current, starting time and duty, class 20 for long starts. Position matters: short-circuit protection (breaker) upstream, overload protection (thermal relay) downstream of the contactor, duties cleanly split. Record setting, trip class and reset mode of every relay on the drawing and hand over a configuration list with the panel.
The coordination core is that the stopping range matches the process: an upstream overload must stop the downstream machines that lose their feed. Wire the upstream thermal NC contact into the downstream control circuits too, directly or through an interposing relay. On a three-machine chain, FR1 trips stop M2 and M3 as well, FR2 stops M2 and M3, FR3 stops only itself. The stopping range is a design decision, not a wiring habit: whether a pump overload stops the spindle instantly depends on the process, since some spindles may coast up to thirty seconds on residual lubrication, in which case the downstream stop goes through a timer.
Every trip must be seen and traced: alarm contacts or flags sum into an alarm circuit lighting the affected station lamp and driving a buzzer. Reset management follows safety grade: in coordinated panels, auto-reset risks a lone upstream machine restarting with its downstream already stopped, so manual reset forcing an investigation is the default; where auto-reset is unavoidable, gate the restart with a downstream-ready contact. Log every trip with time, station and load context, analyze monthly, and any station tripping twice in a month demands a setting or load investigation. Wrong thermal configuration is coordination running without its safety net.
| Item | Wiring | Basis | Check method |
|---|---|---|---|
| Per-machine relays | At each contactor outlet | Nameplate current setting | Against the config list |
| Upstream trip stops downstream | FR NC into downstream circuits | Process stopping range | Simulate trips, verify range |
| Delayed downstream stop | FR NC through a KT | Lubrication coasting needs | Measured delay matches process |
| Alarm indication | Trip contacts into alarm circuit | Perceivable at the duty post | Simulate and watch the lamp |
| Reset mode | Manual for coordinated panels | Prevent lone restarts | Reset requires presence |
| Trip log | Per-event records | Monthly trend analysis | Two trips a month triggers review |
Six configuration items with method, basis and check, verified row by row at acceptance. The single correctness test: whenever any machine overloads, the set of machines that stops matches the process exactly. Meet that and the thermal protection is truly configured.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Overload protection configuration and interlocking follow GB/T 5226.1; thermal relay requirements refer to GB/T 14048.4 (IEC 60947-4-1). Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.