Shorts in control circuits are serious: burnt transformers, welded contactors and whole-cabinet blackouts all trace to missing or wrong protection. This page covers device selection, setting calculations and coordination checks.
Two device families dominate: fuses offer high breaking capacity, current limiting and low cost, ideal for the transformer secondary main; miniature breakers with C or D curves reset easily and suit branch protection, the D curve riding coil inrush while the C curve fits resistive loads. When mixing families, verify grading on the time-current curves so the branch device clears before the upstream fuse for any branch fault.
Set the protection in three steps. Compute normal current as the sum of simultaneous holding powers divided by voltage. Ride the inrush: branch devices at 1.5 to 2 times normal current so coil pull-in does not trip. Check breaking capacity against the prospective short-circuit current, estimated from transformer impedance; a 250VA secondary can deliver several hundred amps, so a 6kA device is comfortably sufficient. Grade the primary and secondary protections of the transformer as well.
A worked example: a 3kVA transformer on AC220V, a 10A primary fuse, a C16 miniature breaker on the secondary main, eight control branches each on C6 or a 2A fuse, and the safety circuit on its own C6. Verify by simulating a short at a branch end so only that branch trips, and measure branch voltage drop under normal load at under 5 percent. Post the configuration table inside the cabinet door with ratings, settings and spare part numbers.
| Location | Recommended device | Setting basis | Check point |
|---|---|---|---|
| Primary side | Fuse | Transformer primary rating | Graded with upstream |
| Secondary main | Fuse or C-curve breaker | 1.2 to 1.5 times secondary rating | Breaking capacity sufficient |
| General branches | C6 or 2A fuse | 1.5 to 2 times loop current | Rides coil inrush |
| PLC and sensors | Separate C6 | 1.5 times load current | Not shared with relays |
| Safety circuit | Independent C6 | Reliability first | Faults spare the function |
| Lighting and heaters | C10 | By load capacity | Kept apart from control |
Protection configuration is a design-once, benefit-forever task: keep the table clear, buy spares by the table and replace like for like. The cardinal sin is refitting a blown fuse one size up; when a short arrives and nothing clears, the transformer pays the price.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Fuse and breaker selection per GB/T 13539 and GB/T 14048.2; control circuit protection per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.