Wiring essentials for star-delta main and control circuits

Star-delta wiring most often fails at the six winding terminals and the cross-connect bridge. This article gives the U1U2V1V2W1W2 layout, the KM2 bridge, and the rule of taking control power from L1L2.

1. How it works

Six wires in the terminal box are marked U1U2, V1V2, W1W2; U1V1W1 are starts to supply, U2V2W2 are ends. In star start U2V2W2 tie to a star point; in delta U2 to W1, V2 to U1, W2 to V1 close the loop. One wrong terminal reverses the motor or loses a phase, so buzz out each group before wiring.

2. Numbers and practice

KM1 feeds three-phase to U1V1W1. KM3 (star) ties U2V2W2. KM2 (delta) bridges U2-W1, V2-U1, W2-V1. KM2 and KM3 share the six terminals but do opposite jobs, so draw the bridge exactly or you short at switch.

3. Pitfalls and fixes

Take 220V control from L1L2, never L1L3 which crosses phases. Match KT and KM coil voltage to control. SB2 start, SB1 stop, KM1 self-hold parallel to SB2, with under-voltage protection on restore.

4. Star-delta terminal wiring table

TerminalStar startDelta run
U1 V1 W1to KM1 outto KM1 out
U2 V2 W2KM3 star pointbridge to W1 U1 V1
KM2 contactsopenbridge U2-W1 V2-U1 W2-V1
KM3 contactsshort U2V2W2open
phaseL1 L2 L3L1 L2 L3
ctrl powerL1L2 220VL1L2 220V

5. Notes

After wiring, no power: meter on KM2 closed shows U1-U2 conducting (delta loop); KM3 closed shows U2V2W2 conducting (star point). No continuity means a wrong terminal, confirm bridge before energizing.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Wiring and marking see GB/T 4728 symbols, safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① One wrong terminal reverses the motor or burns a phase, buzz out each group first.
② KM2 bridge drawn reversed shorts power at delta switch, check the bridge three times.
③ Wrong control phase L1L3 crosses phases and burns coils, always take L1L2.

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.