Everything is fine at low speed but the motor trips the moment high speed engages, so the fault lives in the high-speed branch. This page separates thermal trips from short-circuit trips, then walks four checkpoint lines for thermal trips and the insulation path for short-circuit events.
Classify the trip first. A thermal trip is overload-natured: it happens after some running time, resets and runs again for a while, and the motor is hot. A short-circuit trip is instantaneous: it fires at closing or changeover, the motor stays cold and there may be a bang or flash. The two lead to opposite investigations, current and settings versus insulation and wiring. Identify by which device tripped, the popped thermal relay flag or the instant magnetic release of the breaker, then feel the motor and smell for burning. Never reset blindly: one blind reclose on a short circuit deepens the damage.
For thermal trips walk four lines in order. The dial: the high-speed relay set at the low-speed current is the classic error, a 15A winding set at 12A trips every run. The double-star connection: poor KM3 shorting contacts leave the winding half-connected and overheated, judged by phase-current imbalance beyond ten percent. The mechanical load: fouled fan wheels and starved bearings weigh far more at high speed where torque demand grows with the square of speed, proven by uncoupling and running unloaded. The contacts: eroded KM2 faces drop voltage under high current, raising slip and current in a vicious circle.
For short-circuit trips: megger the winding to frame and between phases, expecting at least one megohm; test the cable and check the terminal box for foreign bridging; inspect the KM2/KM3 sequence, since any instant with both supplies alive is the short window and failed interlocking is the root. After any repair verify in three steps: no-load run with balanced currents, thirty minutes at half load with a temperature record, then a full shift at load watching the relay. Break the trip-reset-trip loop early, because each cycle costs winding life and five cycles mean a rewind.
| Trip nature | Checkpoint line | Measurement | Pass criterion |
|---|---|---|---|
| Thermal | Thermal relay setting | Compare with nameplate high-speed current | Setting equals nameplate value |
| Thermal | Double-star made or not | Phase current imbalance | Below 10% |
| Thermal | Mechanical load | Uncouple and run unloaded | Normal current, no trip |
| Thermal | KM2 contact drop | Voltage across the contacts | Millivolt level |
| Short circuit | Winding and cable insulation | 500V megger | At least 1 megohm |
| Short circuit | Changeover interlock | Simulate changeover, probe contacts | Reliable opening both ways |
Split thermal and short-circuit lines in this table and qualify the trip before probing. Most high-speed trips are settings and shorting-path issues closable in ten minutes; short-circuit events demand full insulation and interlock verification plus the three-step post-repair run before production resumes.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Motor protection coordination follows GB/T 5226.1 and GB/T 14048.4; insulation resistance testing refers to GB/T 1032. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.