A thermal relay appears on drawings at three levels of detail: full drawing, simplified drawing and box designation. This page explains when each style applies and how they convert into one another.
The full style draws both the heating elements (main-circuit rectangles with the wavy line, labelled FR) and the NC control contact (labelled FR auxiliary), tied by the same reference number. It suits teaching schematics and newcomers because the overload cause-and-effect is explicit: overcurrent heats, the bimetal bends, the contact opens. Its cost is sheet space, so complex equipment drawings use it only on key circuits or in manuals.
The simplified style draws only the NC control contact labelled FR and omits the main-circuit elements, since the shared number already links them; this is the standard factory schematic style and saves space. The box style goes further, writing FR plus the setting current beside the device box, used in system block diagrams and list-style sheets. All three are the same device, so a reader must translate freely: a simplified FR contact implies a heating element somewhere in the main circuit.
| Style | What is drawn | Suitable for | Caution |
|---|---|---|---|
| Full | element plus contact | manuals and fault analysis | clearest |
| Simplified | contact only | control schematics | keep the number |
| Box | designation plus current | system block diagrams | state the setting |
| Mixed | styles not unified | confusing | forbidden |
| Linkage | same reference number | common to all three | mandatory |
The three thermal relay styles (full, simplified, box) describe one device, chosen by drawing level: manuals full, schematics simplified, block diagrams by designation. Simplified and box styles must keep the reference number and the setting current, or the link is lost and the crew cannot know what to set on site.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Thermal relay symbols per GB/T 4728.7; setting values per GB/T 5226.1 and IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.