A wrongly placed thermal relay in star-delta either trips at start or refuses to act. This article explains that the thermal must sit on the motor line-current side after KM1, never on the star point at 0.577Ie, with setting rules and consequences.
In delta run the motor line current is Ie, so the thermal relay must measure the true line current and be placed after the KM1 main contacts, near the motor, to reflect overload correctly. Placing it before KM1 also sees line current but is farther from the motor and more exposed to start surges, so prefer the motor-end side for accuracy.
Never place the thermal on the star point. That current is only 0.577Ie, so setting at Ie means it never trips (refuses to act) while setting at 0.577Ie means it trips at star start (nuisance trip); also it loses meaning after switching to delta. The star point is a forbidden zone for the thermal.
Set the thermal at the motor rated current Ie, typically 0.95 to 1.05 Ie, balancing start ride-through and overload trip. Use a three-phase relay to catch open phase, and match the current-transformer ratio if used. Re-calibrate aged bimetal strips periodically; refusal to act is more dangerous than nuisance tripping.
| Position | Current seen | Setting | Result |
|---|---|---|---|
| Line side after KM1 | Ie | 0.95-1.05Ie | correct |
| Supply side | Ie | same | ok but far |
| Star point | 0.577Ie | at Ie | refuse burn |
| Star point | 0.577Ie | at 0.577 | nuisance |
| No thermal | none | none | no protect |
Rule: thermal on line side, set at Ie, star point is forbidden. After install, verify start and run current with a clamp meter so the setting rides through start yet protects overload; do not tuck it on the star point for convenience.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Overload per IEC 60947-4-1, safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.