One machine needs both continuous run and micro jog. This page explains the standard combined wiring so you can build it from the drawing.
The combined circuit builds on the latch: keep start SB2 across the KM auxiliary for run self-hold, and add jog button SB3 whose NO contacts the coil branch directly while its NC sits in the latch branch (the KM auxiliary loop). Press SB2 for run, press SB3 to first break the latch then feed the coil for jog. Both share one KM coil and one motor.
Wiring order: main loop as usual; control supply to stop SB1 (NC) then splits, one path SB2 (NO) parallel KM aux, the other SB3 NO to coil; put SB3 NC inside the latch branch between the KM aux ends; thermal FR NC in series. Key: SB3 must have both NO and NC wired correctly, via a composite button or two buttons.
| Part | Wire | Role |
|---|---|---|
| SB2 | par KM | run |
| SB3 NO | coil | jog on |
| SB3 NC | break latch | jog off |
| SB1 | NC ser | stop |
| FR | NC ser | overload |
| Pit | NO only | to run |
Combined run and jog: run uses SB2 across KM aux, jog uses SB3 NO to coil and NC to break the latch. SB3 needs both contacts wired right. Verify jog stops on release, run holds, and stop works.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage gear GB/T 14048 with IEC 60947; safety GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.